24V 60W 1 Phase / DRP024V060W1B□
Reliability Data
MTBF
Expected Cap Life Time
> 800,000 hrs. as per Telcordia SR-332
I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C
10 years (115Vac & 230Vac, 50% load @ 40°C)
Safety Standards / Directives
Electrical Equipment of Machines
Electrical Equipment for Use in Electrical
Power Installations
Safety Entry Low Voltage
Electrical Safety
Industrial Control Equipment
Hazardous Location / ATEX
(For DRP024V060W1BA)
EN 60204-1 (over voltage category III)
IEC/EN 62477-1 / IEC 62103
TUV Bauart
UL/cUL recognized
CB Scheme
UL/cUL listed
CSA
Hazardous Location
PELV* (EN 60204-1), SELV (EN 60950-1)
EN 60950-1
UL 60950-1 and CSA C22.2 No. 60950-1 (under alternate part
number EOE11010248 of File No. E191395)
IEC 60950-1
UL 508 and CSA C22.2 No. 107.1-01 (under alternate part
number EOE11010248 of File No. E315355)
CSA C22.2 No. 107.1-01 (under alternate part number
EOE11010248 of File No. 181564)
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA
12.12.01:2011 [Class I, Division 2, Group A, B, C, D T4,
Ta= -25°C to +80°C (> +50°C derating)]
II 3G ATEX 2014/34/EU
(For DRP024V060W1BA)
CE
ATEX EN 60079-0:2009, EN 60079-15:2010 [ II 3G Ex nA nC IIC
T4 Gc, Ta= -25°C to +80°C (> +50°C derating)]
Certificate No. EPS 12 ATEX 1 491 X
In conformance with EMC Directive 2014/30/EU and
Low Voltage Directive 2014/35/EU
Material and Parts
Galvanic Isolation
Input to Output
Input to Ground
Output to Ground
For DRP024V060W1BA:
In conformance with Equipment for explosive atmospheres
(ATEX) directive 2014/34/EU
RoHS Directive 2011/65/EU Compliant (EN 50581)
4.0KVac
1.5KVac
1.5KVac
*Output must be earthed in the final unit in order to comply with PELV requirements according to standard EN 60204-1.