English
Language : 

8432210000 Datasheet, PDF (51/58 Pages) Weidmuller – Mini Coupler / Mini Conditioner
Movement and Rotational Speed Monitoring
SMS
SIZA
Rotational speed monitoring
Block diagram
Ordering data
Description
Type
SMS/SIZA
Cat. No.
1110560000
Power supply with delayed turn-off relay output for three-condu-
cutor DC initiators (NPN or PNP).
The transformer supplies the initiator with 24 V DC. The initiator
signal activates the relay, at which time the adjustable turn-off
delay becomes effective. This module is particularly suitable for
monitoring cyclic movements, e.g, down-times monitoring of
conveyor drives, ventilators and pumps or stroke monitoring of
valves, die cutters and drilling heads.
A contact element actuates the initiator at regular intervals. If
these pulses cease, i.e. the proximity switch is continuously
actuated (t4-t6) or deactivated (t1-t3), the relay transmits a signal
after the set time has elapsed. During normal operation, the
time function bridges the gaps between regular pulses (t0-t2)
Technical data
Operating voltage
Initiator type/initiator voltage
Output voltage
Continuous current
Max. switching capacity (resistive load)
Contact
Contact material
Mechanical service life
Time range
Coordination of insulation to VDE DIN 0160, draft11/94
Rated voltage
Rated surge voltage
Overvoltage category
Contamination class
Clearance and creepage distance
EMC
230 Vdc +5 –15%
P or N switched/24 Vdc
250 V
4A
2000 VA
1 changeover contact
AgNi 0.15 gold-flashed
> 107 switching operations
0.5…5 s
300 V
4 kV
III
2
≥ 3 mm
EN 50 081-1/50 082-2
Accessories and dimensions see page 307
Fig. VI
206