Thermo-Signal Conditioners
WAVEANALOG Thermo
thermocouples K, J, T, E,
N, R, S, B configurable
temperature range
-200 °C ... +1820 °C
no adjustment necessary
cold junction compensation
configurable output signal
cross-connectable voltage supply
via cross-connectors
Approvals:
Block diagram
Thermo Select
°C / 0 ... 20 mA,
4 ... 20 mA, 0 ... 10 V
Ordering data
Screw connection
Tension clamp connection
Input/output
Technical data*
Input signal
Types
Output signal
Load resistance
Output signal
Load resistance
Output signal
Load resistance
Accuracy at Tu = 23 °C
Temperature coefficient
Response time without filter
Response time with filter
General
Voltage supply
Power consumption
Current carrying capacity of cross-connection
Open circuit recognition
Operating temperature
Storage temperature
Standards/specifications
EMC standards
Dimensions L / H / W mm
Approvals
Dimensions and accessories see
* TU = 23 °C single module
190
Type
WTS4 Thermo Select
WTZ4 Thermo Select
°C / 0 ... 20 mA
°C / 4 ... 20 mA
°C / 0 ... 10 V
Cat. No.
8432300000
8432310000
Thermocoupler acc. to IEC584 (fully insulated)
K -200 ... +1372 °C
J -200 ... +1200 °C
T -200 ... +400 °C
E -200 ... +1000 °C
N -200 ... +1300 °C
R -50 ... +1760 °C
S -50 ... +1760 °C
B +50 ... +1820 °C
0 ... 20 mA
≤ 500 Ω
4 ... 20 mA
≤ 500 Ω
0 ... 10 V
≥ 1 kΩ
Type K -200°C ...-150°C ± (5K + 0.1% of set range)
-150°C ...1200°C ± (3K + 0.1% of set range)
1200°C ...1372°C ± (4K + 0.1% of set range)
Type J -200°C ...-150°C ± (4K + 0.1% of set range)
-150°C ...1200°C ± (3K + 0.1% of set range)
Type T -200°C ...-150°C ± (5K + 0.1% of set range)
-150°C ...400°C ± (3K + 0.1% of set range)
Type E -200°C ...-150°C ± (4K + 0.1% of set range)
-150°C ...1000°C ± (3K + 0.1% of set range)
Type N -200°C ...-150°C ± (6K + 0.1% of set range)
-150°C ...1300°C ± (3K + 0.1% of set range)
Type R -50°C ...200°C ± (10K + 0.1% of set range)
200°C ...1760°C ± (6K + 0.1% of set range)
Type S -50°C ...200°C ± (10K + 0.1% of set range)
200°C ...1760°C ± (6K + 0.1% of set range)
Type B 50°C ...250°C ± (25K + 0.1% of set range)
250°C ...500°C ± (10K + 0.1% of set range)
500°C ...1820°C ± (6K + 0.1% of set range)
± (200 ppm v. Span
+ 0.075 K) /K
1.1 s
6s
24 Vdc ±20% (19.2 ... 28.8 Vdc)
< 38 mA at Iout = 20 mA
≤2A
LED blinks (output value: > 20 mA and. > 10 V)
0 °C ... +55 °C
-20 °C ... +85 °C
EN 50178, IEC584
EN 50081, EN 50082, EN 55011
92.4 / 112.5 / 12.5
CE, UL, CSA
Page 298 + 308
Switch position/setting options
SW 1
Type 1 2 3
K
J
T
E
N
R
S
B
SW 1
Tmin 4 5 6 7
0 C°
-10 C°
-20 C°
-30 C°
-40 C°
-50 C°
-100 C°
-150 C°
-200 C°
+50 C°
+100 C°
+150 C°
+200 C°
+250 C°
+500 C°
SW 2
Output 6 7
0 - 10 V
0 - 20 mA
4 - 20 mA
SW 2
Span 1 2 3 4 5
100 C°
150 C°
200 C°
250 C°
300 C°
350 C°
400 C°
450 C°
500 C°
550 C°
600 C°
650 C°
700 C°
750 C°
800 C°
850 C°
900 C°
950 C°
1000 C°
1050 C°
1100 C°
1150 C°
1200 C°
1250 C°
1300 C°
1350 C°
1400 C°
1450 C°
1500 C°
1600 C°
1700 C°
1800 C°
Filter 8
off
on
= on
= off