DC/DC-Signal Conditioners
WAVEANALOG DC/DC
voltage supply on output side
2-way-isolation
analogue signal conditioning
galvanic isolation between
input/output signal
Input loop powered
cross-connectable voltage supply
via cross-connectors
CCC DC
4 ... 20 mA / 4 ... 20 mA
Approvals:
CCC DC
4 ... 20 mA / 0 ... 20 mA
CVC DC
4 ... 20 mA / 0 ... 10 V
Block diagram
Ordering data
Screw connection
Tension clamp connection
Input/output
Technical data*
Input signal
Input voltage max.
Input current max
Output signal
Load resistance
Accuracy at Tu=23 °C
Temperature coefficient
Response time
Cut-off frequeny (-3 dB)
Type
Cat. No.
WAS4 CCC DC 8444980000
WAZ4 CCC DC 8444990000
4 ... 20 mA / 4...20 mA
Type
Cat. No.
WAS4 CCC DC 8445010000
WAZ4 CCC DC 8445020000
4 ... 20 mA / 0 ... 20 mA
Type
Cat. No.
WAS4 CVC DC 8445040000
WAZ4 CVC DC 8445050000
4 ... 20 mA / 0 ... 10V
4 ... 20 mA
7V
25 mA
4 ... 20 mA
≤ 500 Ω
± 0.2% of FS
≤ 250 ppm / K of FS
≤ 30 ms (typ. 20 ms)
≥ 15 Hz (typ. 20 Hz)
4 ... 20 mA
7V
25 mA
0 ... 20 mA
≤ 500 Ω
± 0.2% of FS
≤ 250 ppm / K of FS
≤ 30 ms (typ. 20 ms)
≥ 15 Hz (typ. 20 Hz)
4 ... 20 mA
7V
25 mA
0 ... 10 V
≥ 1 kΩ
± 0.2% of FS
≤ 250 ppm / K of FS
≤ 30 ms (typ. 20 ms)
≥ 15 Hz (typ. 20 Hz)
General
Voltage supply
Power consumption
Current carrying capacity of cross-connection
Operating temperature
Storage temperature
Dimensions L / H / W mm
Approvals
24 Vdc ±20%
(19.2 ... 28.8 Vdc)
< 32 mA at Iout = 20 mA
≤2A
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
Coordination of insulation according to EN 50178, 04/98
Rated voltage
Rated surge voltage
Overvoltage category
Contamination class
Clearance and creepage distance
Isolation voltage, voltage strength
Input/output to mounting rail
300 V
4 kV
III
2
≥ 3 mm
4 kVeff / 1 min
Standards/specifications
EMC standards
EN 50178
EN 50081, EN 50082,
EN 55011
24 Vdc ±20%
(19.2 ... 28.8 Vdc)
< 32 mA at Iout = 20 mA
≤2A
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
300 V
4 kV
III
2
≥ 3 mm
4 kVeff / 1 min
EN 50178
EN 50081, EN 50082,
EN 55011
24 Vdc ±20%
(19.2 ... 28.8 Vdc)
< 20 mA at Iout = 10 mA
≤2A
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
300 V
4 kV
III
2
≥ 3 mm
4 kVeff / 1 min
EN 50178
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
*TU = 23 °C single module
Page 298 + 308
Page 298 + 308