English
Language : 

8447130000 Datasheet, PDF (10/58 Pages) Weidmuller – Mini Coupler / Mini Conditioner
RTD Thermocouple Conditioners
• for 2 and 3 wire sensors
MCZ PT100/3 CLP
0…100 °C / 0…120 °C / 0…150 °C / 0…200 °C / 0…300 °C
-50…+150 °C / -40…100 °C
The temperature module converts measurement
values from a PT 100 into analogue measure-
ment signals. The module supplies the sensor
with power. The module is distinguished by its
accuracy and linearity.
Block diagram
Ordering data
for TS 35
Technical data
Input
Connection
Max. wire resistance
Leadwire resistance effect
Supply current
Output
Load
Supply voltage
Residual ripple of supply voltage
Set time
Accuracy
Linearity
Temperature coefficient
Open circuit recognition
EMC
Approvals
Ambient temperature
Storage temperature
Conductor
Conductor cross-section
Overall width
* Putting a bridge between Pins 4 and 5
Dimensions and accessories see
Type
MCZ PT100/3 CLP
MCZ PT100/3 CLP
MCZ PT100/3 CLP
MCZ PT100/3 CLP
MCZ PT100/3 CLP
MCZ PT100/3 CLP
MCZ PT100/3 CLP
0…100 °C
0…120 °C
0…150 °C
0…200 °C
0…300 °C
-50…+150 °C
-40…100 °C
Cat. No.
8425720000
8483680000
8604420000
8473010000
8473020000
8473000000
8604430000
PT 100 (according to IEC 751)
3-wire / 2-wire*
each 50 Ω
max. 0.006 °C/Ω
0.8 mA
4…20 mA**
750 Ω at 24 V
max: 30V / min: 9 V+20mA x RL
max: 1.5 V at 100 Hz
10 ms
Type. 0.2 % max. 0.5 % v. FSR
<0.1 % v. FSR
max. ±250 ppm/°C
yes
EMVG
EN 50081-1
EN 50082-2
CE, UL, CSA
0 °C…+50 °C
-20 °C…+85 °C
AWG 22…12
1.5 mm2
6 mm
** current loop supplied
Page 305
165