BCM400P500T1K8A31 Datasheet, PDF (8/23 Pages) Vicor Corporation – Fixed Ratio DC-DC Converter
BCM400y500x1K8A31
Reported Characteristics
Specifications apply over all line, load conditions, unless otherwise noted; Boldface specifications apply over the temperature range of -40°C ≤ TINTERNAL
≤ 125°C (T-Grade); All other specifications are at TINTERNAL = 25ºC unless otherwise noted.
Monitored Telemetry
• The BCM communication version is not intended to be used without a Digital Supervisor.
ATTRIBUTE
DIGITAL SUPERVISOR
PMBusTM READ COMMAND
ACCURACY
(RATED RANGE)
FUNCTIONAL
UPDATE
REPORTING RANGE RATE
REPORTED UNITS
Input voltage
(88h) READ_VIN
± 5% ( LL - HL )
130 V to 450 V
100 µs
VACTUAL = VREPORTED x 10-1
Input current
(89h) READ_IIN
± 5% ( 10 - 133% of FL)
- 0.85 A to 5.9 A
100 µs
IACTUAL = IREPORTED x 10-3
Output voltage[1]
(8Bh) READ_VOUT
± 5% ( LL - HL )
16.25 V to 56.25 V
100 µs VACTUAL = VREPORTED x 10-1
Output current
(8Ch) READ_IOUT
± 5% ( 10 - 133% of FL )
- 7 A to 47.5 A
100 µs
IACTUAL = IREPORTED x 10-2
Output resistance
(D4h) READ_ROUT
± 5% ( 50 - 100% of FL)
10 µΩ to 40 µΩ
100 ms RACTUAL = RREPORTED x 10-5
Temperature[2]
(8Dh) READ_TEMPERATURE_1
± 7°C ( Full Range)
- 55ºC to 130ºC
100 ms
TACTUAL = TREPORTED
[1] Default READ Output Voltage returned when unit is disabled = -300 V.
[2] Default READ Temperature returned when unit is disabled = -273°C.
Variable Parameter
• Factory setting of all below Thresholds and Warning limits are 100% of listed protection values.
• Variables can be written only when module is disabled either EN pulled low or VIN < VIN_UVLO-.
• Module must remain in a disabled mode for 3 ms after any changes to the below variables allowing ample time to commit changes to EEPROM.
ATTRIBUTE
DIGITAL SUPERVISOR
PMBusTM COMMAND [3]
CONDITIONS / NOTES
Input / Output Overvoltage
Protection Limit
(55h) VIN_OV_FAULT_LIMIT
Input / Output Overvoltage
Warning Limit
(57h) VIN_OV_WARN_LIMIT
Input / Output Undervoltage
Protection Limit
(D7h) DISABLE_FAULTS
VIN_OVLO- is automatically 3%
lower than this set point
Can only be disabled to a preset
default value
ACCURACY
(RATED RANGE)
± 5% ( LL - HL )
± 5% ( LL - HL )
± 5% ( LL - HL )
FUNCTIONAL
REPORTING
RANGE
DEFAULT
VALUE
130 V to 435 V 100%
130 V to 435 V 100%
130 V or 260 V 100%
Input Overcurrent
Protection Limit
(5Bh) IIN_OC_FAULT_LIMIT
Input Overcurrent
Warning Limit
(5Dh) IIN_OC_WARN_LIMIT
Overtemperature Protection
Limit
(4Fh) OT_FAULT_LIMIT
Overtemperature
Warning Limit
(51h) OT_WARN_LIMIT
Turn on Delay
(60h) TON_DELAY
Additional time delay to the
Undervoltage Startup Delay
± 5% ( 10 - 133% of FL) 0 to 5.625 A 100%
± 5% ( 10 - 133% of FL) 0 to 5.625 A 100%
± 7°C ( Full Range)
0 to 125°C
100%
± 7°C ( Full Range)
0 to 125°C
100%
± 50 µs
0 to 100 ms
0 ms
[3] Refer to Digital Supervisor datasheet for complete list of supported commands.
BCM® Bus Converter
Page 8 of 23
Rev 1.3
05/2015
vicorpower.com