Electrical Specifications (Cont.)
Specifications valid at 48VIN, 100% rated load and 25ºC ambient, unless otherwise indicated.
­Attribute
Symbol
Conditions / Notes
IB0xxQ096T70xx-xx
Min
Typ
Max
Unit
Common Output Specifications
Output power *
0
750
W
Output current
Output start up load
Effective output resistance
P ≤ 750W
of IOUT max, maximum output capacitance
70
A
15
%
3.1
mΩ
Line regulation (K factor)
Current share accuracy
Efficiency
VOUT = K • VIN @ no load
Full power operation; See Parallel Operation
on page 15; up to 3 units
0.198 0.200 0.2020
10
%
50% load
See Figures 1–3
97.8
98.1
%
Full load
Internal output inductance
Internal output capacitance
Load capacitance
Output voltage ripple
Output overload protection
threshold
Overcurrent protection
time constant
Short circuit current response time
Switching frequency
Dynamic response – load
VOUT overshoot / undershoot
VOUT response time
Dynamic response – line
VOUT overshoot
See Figures 1–3
96.9
0
20MHz bandwidth (Figure 16),
using test circuit in Figure 24
Of IOUT max, will not shut down when started into max
COUT and 15% load.
105
Auto restart with duty cycle < 10%
Load change: ±25% of IOUT max,
Slew rate (dI/dt) = 1A/µs
See Figures 11–14
Line step of 5V in 1µs, within VIN operating range.
(CIN = 500µF, CO = 350µF)
(Figure 15 illustrates similar converter response
when subjected to a more severe line transient.)
97.3
1.6
92.4
60
1.0
1
4500
150
%
nH
µF
µF
mVp-p
150
%
1.2
ms
1.5
µs
MHz
100
mV
µs
1.25
V
Pre-bias voltage
Unit will start up into a pre-bias voltage on the output
0
12
VDC
* Does not exceed IPC-9592 derating guidelines. At 70ºC ambient, full power operation may exceed IPC-9592 guidelines, but does not exceed component
ratings, does not activate OTP and does not compromise reliability.
IBC Module
Page 6 of 18
Rev 1.2
09/2016
vicorpower.com
800 927.9474