1.1 APPLICATION CHARACTERISTICS
All specifications are at TJ = 25ºC unless otherwise noted. See associated figures for general trend data.
ATTRIBUTE
No load power
Inrush current peak
Efficiency (ambient)
Efficiency (hot – 100°C)
Output resistance (-40°C)
Output resistance (25°C)
Output resistance (100°C)
Output voltage ripple
VOUT transient (positive)
VOUT transient (negative)
Undervoltage lockout
response time
Output overcurrent
response time
Overvoltage lockout
response time
SYMBOL
PNL
INR-P
η
η
ROUT_C
ROUT_R
ROUT_H
VOUT-PP
VOUT-TRAN+
VOUT-TRAN-
TUVLO
CONDITIONS / NOTES
VIN = 48 V, PC enabled; See Figure 1
COUT = 500 µF, POUT = 120 W
VIN = 48 V, POUT = 120 W
COUT = 500 µF
VIN = 48 V, POUT = 120 W
COUT = 500 µF
VIN = 48 V
VIN = 48 V
VIN= 48 V
COUT = 0uF, POUT = 120 W @ VIN = 48,
VIN = 48 V
IOUT_STEP = 0 TO 10.55 A,
ISLEW >10 A/us; See Figure 12
IOUT_STEP = 10.55 A to 0 A,
ISLEW > 10 A/us; See Figure 11
TOCP
12 < IOCP < 25 A
TOVLO
TYP
1.75
6
95
94
35
44
56
160
1.4
1.3
2.4
4.4
2.4
UNIT
W
A
%
%
mΩ
mΩ
mΩ
mV
V
V
us
ms
µs
BCM® Bus Converter
Page 5 of 16
Rev 1.2
07/2015
vicorpower.com
800 927.9474