SU80KTV Datasheet, PDF (3/5 Pages) Tripp Lite. All Rights Reserved – SmartOnline 277-480V 3-Phase Wye 80kVA Modular 3-Phase UPS System, On-line Double-Conversion UPS for North America
Output Receptacles
Hardwire
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 97A (per phase, online)
Nominal Input Voltage(s) Supported 277/480V (3ph wye)
UPS Input Connection Type
Hardwire
UPS Input Connection Description 277/480V (3-Phase, 4 Wire, wye)
Input Phase
3-Phase
BATTERY
Expandable Battery Runtime
External Battery Pack Compatibility
Expandable Runtime Description
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Battery Replacement Description
Battery set sold separate
BP480V103 ; BP480V140 ; BP480V26B ; BP480V40C ; BP480V55 ; BP480V78 ; BP480V200 ; BP480V300 ;
BP480V400 ; BP480V500
External battery pack wiring is contractor supplied
+/- 240VDC
2 - 4 hours from 10% to 90%
Hot-swappable, replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
Online, double-conversion power conditioning
Maintains continuous operation without using battery power during overvoltages to 348/603 (3-Phase, 4-Wire, wye)
Maintains continuous operation without using battery power during brownout / undervoltage conditions to 218/378
(3-Phase, 4-Wire, wye)
USER INTERFACE, ALERTS & CONTROLS
Switches
ON button turns UPS's inverter ON. OFF button turns UPS's inverter OFF. LCD Display Control Buttons browses
through and selects items displayed on LCD screen. Emergency Power Off button turns UPS output OFF and
disables Bypass output. Manual Bypass breaker bypasses the UPS's inverter during maintenance.
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch
Audible Alarm
Alarms warn against a variety of operational conditions: low-battery, overload, shutdown, bypass and more
LED Indicators
4-LED Display: Displays normal AC input, on battery power, bypass input and fault conditions
SURGE / NOISE SUPPRESSION
EMI / RFI AC Noise Suppression
Yes
AC Suppression Joule Rating
4675
AC Suppression Response Time
Instantaneous
3/5