SU80KTV Datasheet, PDF (2/5 Pages) Tripp Lite. All Rights Reserved – SmartOnline 277-480V 3-Phase Wye 80kVA Modular 3-Phase UPS System, On-line Double-Conversion UPS for North America
cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval. An Emergency Power Off button turns UPS
output OFF and disables Bypass output. Built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities. A
start-up service program is recommended to enhance the reliability of the installation.
Features
N+1 configuration: four self-contained, redundant 20kVA power modules can be hot-swapped (with the load powered) if maintenance is required
1+1 configuration: connect two SU80KTV models in parallel to provide fail-safe redundancy or to increase capacity
High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology create low input Total Harmonic Distortion
(THDi)
Extremely efficient operation (up to 96%) saves money by lowering electricity consumption
True on-line, double conversion UPS with IGBT technology provides pure, sine wave AC output at all times
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
80,000VA/64,000W power capacity with 3-phase, hardwire 277/480VAC input/output connections
Features a wide input voltage correction range (218-348/378-603VAC at full load)
Precision +/-1% output voltage regulation
A stand-alone hardwired external battery module (Models BP480V26B and BP480V40C, available separately from Tripp Lite) is required for operation
and to provide battery backup support. Additional external battery modules can be connected for extended runtime.
Front panel combination LCD/LED display includes a real-time event log screen with up to 500 events listed
Dynamic battery management screen optimizes battery function to lengthen service life and allows cold restart of UPS
Built-in RS-232 communication port works with included PowerAlert Software to provide shutdown commands and reporting on a single server
Accessory slot accepts an optional internal SNMP card (model # SNMPWEBCARD) for remote shutdowns, reboots and more
Emergency Power Off button turns UPS output OFF and disables Bypass output
Built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities
Start-up service program is recommended to enhance the reliability of the installation
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
80000
Output kVA Capacity (kVA)
80
Output Watt Capacity (Watts)
64000
Output kW Capacity (kW)
64
Power Factor
0.8
Crest Factor
3:1
Nominal Output Voltage(s)
Supported
277/480V; 3-Phase Wye
Frequency Compatibility
50 / 60 Hz
Output Voltage Regulation (Line
Mode)
+/-1%
Output Voltage Regulation (Battery
Mode)
+/-1%