English
Language : 

SU80KTV Datasheet, PDF (1/5 Pages) Tripp Lite. All Rights Reserved – SmartOnline 277-480V 3-Phase Wye 80kVA Modular 3-Phase UPS System, On-line Double-Conversion UPS for North America
SmartOnline 277/480V 3-Phase Wye 80kVA Modular
3-Phase UPS System, On-line Double-Conversion
UPS for North America
Highlights
80,000 VA (80kVA) tower UPS
with 4 hot-swappable power
modules
MODEL NUMBER: SU80KTV
N+1 redundant modular
architecture helps ensure 100%
availability
1+1 parallel capability allows for
system redundancy or increased
capacity
Low THDi saves installation costs
by allowing 1:1 generator sizing
3-phase hardwire (277/480VAC)
input/output. Wide input voltage
correction range
(218-348/378-603VAC at full
load)
On-line, double-conversion
operation with zero transfer time;
Description
Tripp Lite's SU80KTV (80kVA) SmartOnline Modular 3-Phase Intelligent, True On-Line UPS System provides
100% system availability with N+1 modular architecture and 1+1 parallel capability. In an N+1 configuration, the
SU80KTV features four self-contained, redundant 20kVA power modules that can be hot-swapped (with the load
IGBT technology; extremely
efficient operation (up to 96%)
Runtime is expandable via
external battery cabinet options
powered) if maintenance is required. Connect two SU80KTV models in parallel (1+1 configuration) to provide
fail-safe redundancy (two 80kVA models supporting a 80kVA load) or to increase capacity (two 80kVA models
supporting a 160kVA load).
Package Includes
SU80KTV UPS System
PowerAlert Software and cabling
The SU80KTV provides mission-critical equipment with the highest level of power protection available. Large
capacity 80,000VA/64,000W UPS continually converts incoming AC power into filtered DC power, and then
resynthesizes it back into AC power with a pure sine wave. Perfectly regulated, continuous sine wave output with
zero transfer time offers compatibility with all equipment types. The SU80KTV's high input power factor,
Parallel cable (for 1+1 operation)
Instruction manual and startup
checklist
Warranty information
advanced IGBT inverter technology and Digital Signal Processor (DSP) technology create less than 3% input Total Harmonic Distortion (THDi). With
SU80KTV's low THDi, generators run cooler and last longer, allowing managers to save installation costs by installing a generator with a capacity equal to
their equipment load (a 1:1 ratio). Extremely efficient operation (up to 96%) saves money by lowering electricity consumption. Hardwire input and output
connections support a variety of permanent or PDU style power connections. The SU80KTV features 277/480VAC, 3-phase, 4-wire (plus ground), wye input
and output. It also features a wide input voltage correction range (218-348/378-603VAC at full load). Frequency is 50 or 60 Hz (auto-selectable). The
SU80KTV features a single small-footprint tower power module. A stand-alone hardwired external battery module (Models BP480V26B or BP480V40C with
matching battery cabinets, available separately) is required for operation and to provide battery backup support. Additional external BP480V26B or
BP480V40C battery modules can be connected for extended runtime. Other battery cabinets for extended runtime solutions also available; contact Tripp Lite
for more information. A manual bypass breaker as well as an automatic bypass function ensure 100% availability of connected equipment by safely passing
through AC power if the UPS requires maintenance. A built-in RS-232 communication port works with included PowerAlert Software to provide shutdown
commands and reporting on a single server. An accessory slot accepts an optional internal SNMP card (Model SNMPWEBCARD) for remote shutdowns,
reboots and more. Front panel combination LCD/LED display alerts users to a variety of UPS operational modes and conditions. The LCD display includes a
real-time event log screen with up to 500 events listed. A dynamic battery management screen optimizes battery function to lengthen service life and allows
1/5