DRS24D25 Datasheet, PDF (4/4 Pages) Teledyne Technologies Incorporated – Single Output to 30A 510 Vac DIN-Rail Solid-State Relay with Diagnostics | |||
|
◁ |
STATUS OUTPUT ANSWER CHARACTERISTICS
Min
Max Unit
Voltage Range
1
32
V
Output Current
0.1
A
On Resistance
2
â¦
Open Delay (to1) (faults) 70
ms
Total Open Delay (to2) (faults) 120
ms
Close Main Delay (tc1) (tc2)
20
ms
Maximum Cable Length for Open Load 40
m
Series DRS
DIAGNOSTIC DESCRIPTION
Control
0
1
Control
LED
â
â
0
â
1
â
0
â
0
â
1
â
1
â
Main
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Load
x
x
OK
OK
Open
OK
Open
OK
SSR
x
x
Output
LED
â
â
OK
â
OK
â
OK
â
Short-Circuit
â
OK
â
Short-Circuit
â
Output
Status
Open
Open
Closed
Closed
Open
Open
Open
Open
Figure 7 â DRS relay
Main
OPEN MAIN
On
Control
Off
Current
ton
Open Status output
Closed
to1
to2
tc1
to1
to2
DIAGNOSTICS OVERVIEW
OPEN LOAD
SHORT-CIRCUIT
ON OUTPUT
⢠Output status is normally closed without
failure on the relay and the load. The
output LED is normally ON:
⢠In case of failure on the load (open) or
on the SSR (short-circuit condition):
- the status is open
- the output LED is switched OFF
toff
tc2
to1
tc1
to2
Control LED
Figure 8 â DRS relay
Output LED
DIN-RAIL MOUNTING
Mounting
Dismounting
DIN rail
connected
to protection
wire (ground)
Figure 9 â DRS relay
PANEL MOUNTING
M5
M4
3.47±.08
(88±2)
.5 (12.7)
Figure 10 â DRS relay
CONNECTIONS
wires
L
L
(mm2)
control
1 x (0.75-->2.5)
L = 6mm
Power
1 x (1.5-->16) 1 x (1.5-->10)
L = 10mm
torque
screwdriver
0.4N.m
(0.6N.m max)
3.5 x 0.5mm
1.2N.m
(1.8N.m max)
Pozidriv2/
0.8 x 5.5 (1 x 6)
Figure 11 â DRS relay
DRS 4
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE © 2003 TELEDYNE RELAYS
DRS\032003\Q1
|