FNP1500_10 Datasheet, PDF (4/17 Pages) Power-One – Front-Ends & FNR-3 Power Shelves Data Sheet
FNP1500/1800 Front-Ends
& FNR-3 Power Shelves Data Sheet
Output Specifications, 12Vout Models
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
Parameter
Nominal output voltage
Output voltage set point accuracy
Output voltage trimming
Conditions/Description
Io = 64.5 A
Vi = 230 VAC, Io1 = 65.5 A, TC = 25 °C
(Factory setting)
Adjustable via I2C (Vo1 set)
Adjustable via Margin pin (R input)
Min
11.93
-0.42
7
6.2
Nominal
current
output 1
Nominal
current
output 1
Current
limit
output 1
Current
limit
output 1
FNP1500-12G
FNP1800-12G
FNP1500-12G
FNP1800-12G
Nominal current output 2
Current limit output 2
Static line regulation output 1
Static load
regulation
output 1
(droop
characteristic)
FNP1500-12G
Static load
regulation
output 1
(droop
characteristic)
FNP1800-12G
Static load regulation
output 2 (droop characteristic)
Dynamic
load
regulation
Current
Share
Start-up time
FNP1500-12G
& FNP1800-12G
FNP1500-12G
& FNP1800-12G
FNP1500-12G
FNP1800-12G
Output voltage ripple and noise
(Filter 10nF/10µF)
Remote sense
1 FNP1800-12G max is 12V.
Io1 nom @ Vi =108 VAC – 264 VAC, Po 1.5 kW
Io1 nom @ Vi = 85 VAC – 105 VAC, Po 1.2 kW
Io1 nom @ Vi =108 VAC – 264 VAC, Po 1.75 kW
Io1 nom @ Vi =108 VAC – 180 VAC, Po 1.5 kW
Io1 nom @ Vi = 85 VAC – 105 VAC, Po 1.2 kW
Io1 max @ Vi = 108 VAC – 264 VAC droop hiccup
Io1 max @ Vi = 85 VAC – 105 VAC droop hiccup
Io1 max @ Vi = 180 VAC – 264 VAC high droop
Io1 lim @ Vi = 180 VAC – 264 VAC hiccup
Io1 max @ Vi = 108 VAC – 180 VAC high droop
Io1 lim @ Vi = 108 VAC – 180 VAC hiccup
Io1 max @ Vi = 85 VAC – 105 VAC high droop
Io1 lim @ Vi = 85 VAC – 105 VAC hiccup
Io2 nom @ Vi = 85 VAC – 265 VAC, Po 12 W
Io2 max @ Vi = 85 VAC – 265 VAC
Vi min - Vi max, 50 % Io nom, Ta = 25 °C
Vi = 230 V, 5 - 100 % Io nom
Full load to no load [0..129 A] at Vo set = 12V
dVo1 over the setting range [7 to 13V]
Vi = 230 V, 5 - 100 % Io nom
Full load to no load [0..150 A] at Vo set = 12V
dVo1 over the setting range [7 to 13V]
-0.5
11.64
-0.36
11.52
-0.48
Full load to no load @ Vi = 85 VAC – 265 VAC
Load change 50% <─>100% Io nom, dIo/dt =1A/s
Voltage deviation (droop + over- or undershoot)
-2
Max. recovery time to within 1% of Vo1 nom
Difference in current between two units for Vo1 above
10 % load.
Time required for output within regulation after initial
application of AC-input (Vi nom, Io nom)
after removal of inhibit (Vi nom, Io nom)
Vi nom, Io nom, 20 MHz bandwidth
Vo1
Vo2
Total compensation for cable losses
Nom
12
12
12
129.0
101.8
150.0
129.0
101.8
147.4
120.2
156.4
168.4
135.4
147.4
108.2
120.2
1.0
1.5
- 5.58
12
- 5.58
12
0.4
12.9
15
100
Max
12.05
+0.42
13 1
Vo1 set
129.0
Units
VDC
VDC
% Vo1 nom
VDC
VDC
ADC
ADC
150.0
ADC
ADC
ADC
ADC
ADC
1.0
0.5
12.36
+0.36
ADC
ADC
ADC
ADC
ADC
ADC
ADC
ADC
% Vo nom
mV/A
VDC
VDC
12.36
+0.36
mV/A
VDC
VDC
VDC
2
% Vo nom
400
s
ADC
ADC
1.5
s
ms
120
mVpp
120
mVpp
500
mV
MCD10074 Rev. 1.2, 15-Apr-10