FNP1500_10 Datasheet, PDF (3/17 Pages) Power-One – Front-Ends & FNR-3 Power Shelves Data Sheet
FNP1500/1800 Front-Ends
& FNR-3 Power Shelves Data Sheet
Safety Specifications
Maximum electric strength testing is performed in the factory according to EN 550116, IEC/EN 60950, and UL 60950.
Input-to-output electric strength tests should not be repeated in the field. Power-One will not honor any warranty claims resulting
from electric strength field tests.
Parameter
Agency approvals
Insulation safety rating
Electric strength test voltage
Conditions/description
UL60950, (UL) CSA 60950 (cUL),
EN 60950(TÜV), CE Mark for LVD
Input to case
Input to output
Output to case
Input to case
Input to output
Output to case
Output 1 to output 2
Min Nom Max
Basic
Reinforced
Functional
2.12
4.2 1
0.5
0.1
1 Subassemblies are pre-tested with 4.2 kVDC in accordance with EN50116 and IEC/EN60950.
Unit
kVDC
kVDC
kVDC
kVDC
EMC Specifications
Parameter
Electrostatic discharge
Electromagnetic field
Electrical fast transients/burst
Surge
Voltage dips and interruptions
RF conducted immunity
Emissions conducted
Emissions radiated
Harmonics
Voltage fluctuation and flicker
Voltage sag
Description
IEC/EN 61000-4-2, level 4
IEC/EN 61000-4-3, level 3
IEC/EN 61000-4-4, level 3
IEC/EN 61000-4-5, level 3
IEC/EN 61000-4-11
IEC/EN 61000-4-6
CISPR 22/EN 55022/EN 61204
CISPR 22/EN 55022/EN 61204
IEC/EN 61000-3-2
IEC/EN 61000-3-3
SEMI F47-0200 (High Line 230V)
Criterion
Performance criterion B
Performance criterion A
Performance criterion B
Performance criterion B
Performance criterion B or better
10 VAC, AM 80 %, 1 kHz
Performance criterion A
Class B
Class A
Class B
Pass
Pass
Input Specifications
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
Parameter
Input voltage
Input frequency
Turn-on input voltage
Turn-off input voltage
Inrush current limitation
Hold-up time
Power factor
Efficiency
Max input current
Input connector
1 87% for FNP1500-12
Conditions/description
Ramping up
Ramping down
115/230 VAC acc. ETS 300 132-1
< 100 ms
After last AC line peak ,Vi = 230 VAC, Po nom
Vi nom, Io nom
Vi = 230 VAC, Io nom, TC = 25 °C
Min
Nom
85
230
47
50/60
79
70
20
0.95
89 1
90
16A – 20 A / 250 VAC; according to IEC320 C19
Max
264
63
85
78
50
20
Unit
VAC
Hz
VAC
VAC
Apk
ms
W/VA
%
Arms
MCD10074 Rev. 1.2, 15-Apr-10
Page 3 of 17