English
Language : 

TMC81C01A Datasheet, PDF (8/13 Pages) PHOENIX CONTACT – Thermal magnetic UL 489 miniature circuit breakers
TMC 8...
Conformance
IEC 60068-2-6 (Sinusoidal vibration)
IEC 60068-2-27 (Shock)
IEC 60068-2-11 (Corrosion)
IEC 60068-2-75 (Humidity)
Approval
Test center
UL
UL
UL
UL
TÜV
3.1
10000
Trip curve
1000
Standard
UL 489/CSA-C22.2 No. 5
UL 489/CSA-C22.2 No. 5
UL 489/CSA-C22.2 No. 5
UL 489/CSA-C22.2 No. 5
IEC/EN 60947-2
Ambient temperature +30°C
No-trip current
Trip current
1.05x In
1.30x In
Curve B magnetic trip current 4x In (±20%)
Curve C magnetic trip current 8x In (±20%)
Curve D magnetic trip current 12x In (±20%)
±0.38 mm (10-57 Hz), 5g (57-500 Hz)
10 frequency cycles per axis
30g, 11 ms
96 h in 5% salt mist
48 h at 95% relative humidity, 40°C
Rated voltage
277 V AC, 60 V DC (TMC 81...)
120 V AC, 60 V DC (TMC 81...)
480 V AC, 125 V DC (TMC 82/83...)
240 V AC, 125 V DC (TMC 82/83...)
230/400 V AC
Nominal current range
1 ... 32 A
35 ... 63A
1 ... 32 A
35 ... 63A
1 ... 63 A
Magnetic tripping currents are increased by 30%
on DC supplies at ambient temperature 30°C
3.2 Dimensions
116
45
17,6
100
Figure 2 TMC 81... dimensions (mm)
10
116
45
35,3
1
0,1
B
CD
0,01
0,8 1
2
4
6 8 10
2
Figure 1 Trip curves
3644_en_A
Figure 3 TMC 82... dimensions (mm)
116
45
52,9
0
Figure 4 TMC 83... dimensions (mm)
PHOENIX CONTACT 8/13