English
Language : 

HC2-HP-DC12V Datasheet, PDF (8/15 Pages) Panasonic Semiconductor – Relay for control panel of 1A to 10A (1c/2c/3c/4c)
HC
2) Specifications
Characteristics
Contact
Rating
Electrical
characteristics
Mechanical
characteristics
Item
Arrangement
Contact resistance (Initial)
Contact material
Nominal switching capacity
(resistive load)
Max. switching power
(resistive load)
Max. switching voltage
Max. switching current*4
Nominal operating power
Min. switching capacity
(Reference value)*1
Insulation resistance (Initial)
Breakdown
voltage
(Initial)
Between open
contacts
Between contact
sets
Between contact
and coil
Temperature rise (coil)
(at 70°C 158°F)
Operate time (at 20°C 68°F)*2
Release time (at 20°C 68°F)*2
Shock
resistance
Functional
Destructive
Vibration
resistance
Functional
Destructive
Mechanical
Expected life
Electrical
Conditions
Unit weight
Conditions for operation,
transport and storage*3
Max. Operating speed
1 Form C
Specifications
2 Form C
3 Form C
4 Form C
4 Form C (twin)
Max. 30 mΩ (By voltage drop 6 V DC 1A)
Ag alloy (cd free) + Au flash
AgNi type + Au clad
10A 250V AC
7A 250V AC
7A 250V AC
5A 250V AC
3A 250V AC
2,500VA
1,750VA
1,750VA
1,250VA
750VA
250VAC
10A
7A
7A
5A
3A
AC (50Hz): 1.3VA, AC (60Hz): 1.2VA, DC: 0.9 to 1.1W
1mA 1V DC
100µA 1V DC
Min. 1,000MΩ (at 500V DC) Measurement at same location as “Breakdown voltage” section.
700 Vrms for 1min. (Detection current: 10mA.)
700 Vrms for 1min. (Detection current: 10mA.)
2,000 Vrms for 1min. (Detection current: 10mA.)
Max. 80°C 176°F (By resistive method, nominal coil voltage)
Max. 20ms (Nominal coil voltage applied to the coil, excluding contact bounce time.)
Max. 20ms (Nominal coil voltage applied to the coil, excluding contact bounce time.) (without diode)
Min. 196 m/s2 (Half-wave pulse of sine wave: 11 ms; detection time: 10µs.)
Min. 980 m/s2 (Half-wave pulse of sine wave: 6 ms.)
10 to 55 Hz at double amplitude of 1 mm (Detection time: 10µs.)
10 to 55 Hz at double amplitude of 2 mm
Min. 5×107: AC coil type (at 180 times/min.); Min. 108: DC coil type (at 180 times/min.)
Min. 2×105
resistive load
(at 20 times/min.)
Min. 2×105
resistive load
(at 20 times/min.)
Min. 105
resistive load
(at 20 times/min.)
Min. 2×105
resistive load
(at 20 times/min.)
Min. 2×105
resistive load
(at 20 times/min.)
Ambient temperature: –50°C to +70°C –58°F to +158°F (without LED); –50°C to +60°C –58°F to +140°F (with LED)
Humidity: 5 to 85% R.H. (Not freezing and condensing at low temperature)
20 times/min. (at max. rating)
Approx. 30g 1.06 oz
Notes: *1. This value can change due to the switching frequency, environmental conditions and desired reliability level, therefore it is recommended to check this with the
actual load.
*2. For the AC coil types, the operate/release time will differ depending on the phase.
*3. The upper limit of the ambient temperature is the maximum temperature that can satisfy the coil temperature rise value. Refer to Usage, transport and storage
conditions in NOTES.
*4. When using the socket and terminal socket, be sure to verify the max. continuous current.
3) Switching capacity and expected life
(1) Electrical (at 20 times/min.)
Load
Voltage
AC
Resistive (cos ϕ = 1)
Inductive (cos ϕ 0.4)
125V AC
250V AC
125V AC
250V AC
10A
10A
5A
3A
1 Form C
7A
7A
3A
2.5A
5A
5A
2A
1.5A
7A
7A
3.5A
2A
2 Form C
5A
5A
2.5A
1.5A
3A
3A
1.5A
1A
7A
7A
—
—
3 Form C
—
—
3.5A
2A
5A
5A
—
—
5A
5A
2A
1A
4 Form C
3A
3A
1A
0.8A
2A
2A
0.5A
0.4A
4 Form C (twin)
3A
3A
1A
0.8A
DC
Resistive
Inductive
30V DC
30V DC
—
—
3A
1A
—
—
—
—
3A
0.6A
—
—
—
—
—
—
3A
0.4A
—
—
3A
0.4A
—
—
3A
—
Expected life
Min. 2×105
Min. 5×105
Min. 106
Min. 2×105
Min. 5×105
Min. 106
Min. 105
Min. 2×105
Min. 5×105
Min. 2×105
Min. 5×105
Min. 106
Min. 2×105
(2) Mechanical (at 180 times/min.)
AC coil type: Min. 5×107; DC coil type: Min. 108
ASCTB4E 201302-T
Panasonic Corporation Automation Controls Business Unit industrial.panasonic.com/ac/e/