English
Language : 

H3CRFAC100240 Datasheet, PDF (9/23 Pages) Omron Electronics LLC – Solid-state Twin Timers
H3CR-G
■ Ratings
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz)
Operating voltage range
85% to 110% of rated supply voltage
Power reset
Minimum power-opening time: 0.5 s
Power consumption
100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC
200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC
Control outputs
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
Note: 1. Do not use an inverter output as the power supply. Refer to Safety Precautions for All Timers for details.
2. Refer to Safety Precautions for All Timers when using the Timer together with a 2-wire AC proximity sensor.
■ Characteristics
Accuracy of operating
time
Setting error
Accuracy of Star-delta
transfer time
Reset voltage
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Impulse withstand
voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
EMC
Case color
Degree of protection
Weight
±0.2% FS max.
±5% FS ±50 ms max.
±25% FS + 5 ms max.
10% max. of rated voltage
±0.2% FS max.
±1% FS max.
100 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
3 kV (between power terminals)
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Malfunction: 8 kV
Destruction: 15 kV
Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Destruction: 980 m/s2 three times each in six directions
Malfunction: 294 m/s2 three times each in six directions
Operating: −10°C to 55°C (with no icing)
Storage: −25°C to 65°C (with no icing)
Operating: 35% to 85%
Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)
(EMI)
EN61812-1
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
(EMS)
EN61812-1
Immunity ESD:
IEC61000-4-2:
6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves:
IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900±5 MHz) (level 3)
Immunity Conducted Disturbance: IEC61000-4-6:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
IEC61000-4-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity Surge:
IEC61000-4-5:
1 kV line to line (level 3)
2 kV line to ground (level 3)
Light Gray (Munsell 5Y7/1)
IP40 (panel surface)
H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g
Note: Refer to the Life-test Curve.
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
9