English
Language : 

H3CRFAC100240 Datasheet, PDF (8/23 Pages) Omron Electronics LLC – Solid-state Twin Timers
Accessories (Order Separately)
H3CR-G
Flush Mounting Adapter
Name/specifications
Mounting Track
End Plate
Spacer
Protective Cover
Track Mounting/
Front Connecting Socket
Back Connecting Socket
Time Setting Ring
Panel Cover (See note 2)
Hold-down Clip (See note 3)
50 cm (l) × 7.3 mm (t)
1 m (l) × 7.3 mm (t)
1 m (l) × 16 mm (t)
8-pin
8-pin, finger safe type
8-pin
8-pin, finger safe type
Setting a specific time
Limiting the setting range
Light gray (5Y7/1)
Black (N1.5)
Medium gray (5Y5/1)
For PL08 and PL11 Sockets
For PF085A Socket
Models
Y92F-30
Y92F-70
Y92F-71
PFP-50N
PFP-100N
PFP-100N2
PFP-M
PFP-S
Y92A-48B
P2CF-08
P2CF-08-E
P3G-08
P3G-08 with Y92A-48G (See note 1)
Y92S-27
Y92S-28
Y92P-48GL
Y92P-48GB
Y92P-48GM
Y92H-1
Y92H-2
Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 Socket.
2. The Time Setting Ring and Panel Cover are sold together.
3. Hold-down Clips are sold in sets of two.
Specifications
■ General
Item
Functions
Pin type
Operating/Reset method
Output type
Mounting method
Approved standards
H3CR-G8L
H3CR-G8EL
Star-delta timer
Star-delta timer with instantaneous output
8-pin
Time-limit operation/Self-reset
Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Instantaneous: SPST-NO
DIN track mounting, surface mounting, and flush mounting
UL508, CSA C22.2 No.14, NK, Lloyds
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
■ Time Ranges
Time unit
Full scale setting 6
12
60
120
Star operation time ranges
0.5 to 6 s
1 to 12 s
5 to 60 s
10 to 120 s
Star-delta transfer time Programmable at 0.05 s, 0.1 s, 0.25 s or 0.5 s
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
8