J Wiring Precautions
• Use ducts to separate input leads and power lines in order to protect the Controller and its lines from external noise.
• Solderless terminals are recommended when wiring the Controller.
• Tighten the terminal screws using a torque no greater than 0.78 N S m, or 8 kgf S cm max. Be careful not to tighten the terminal
screws too tightly.
Power Blocks for E5CK--T
The E5CK-T has independent power supplies for each of the terminal blocks shown below.
Note: The power supplies for blocks C (exclude relay output) and D are shared for the following option board:
E53-CKB or E53-CKF Option Board
E5CK-T
A
C
5 11 12 10
4
9
3
8
C2
7
1 13 14 6
D
B
J E5CK-T Wiring
Power Supply
Input 100 to 240 VAC to terminal numbers 4 and 5 according to the specification.
5
11 12 10
4
9
3
8
2
7
1
13 14
6
Input
Connect the input to terminal numbers 6 to 8 as follows according to the input type.
5
11 12 10
4
9
3
8
2
7
1
13 14
6
8
8
-
7
7
6
+
Thermocouple
6
Platinum resistance
thermometer
8
-
7
V
6
+
Voltage input
8
-
7
mA
6
+
Current input
TC ⋅ PT
V
I
Match the inputs with the internal jumper settings for each input type. For thermocouple or platinum resistance thermometer inputs, set
the inputs to a common position (TC/PT) as the temperature input.
Control Output
Terminal numbers 11 and 12 are for control output 1 (OUT1). The five output types and internal equalizing circuits are available according
to the output board.
5
11 12 10
4
9
3
8
2
7
13 14
1
6
11
12
Relay
E53-R4R4
+
+v
11
+
+v 11
L
L
GND
12
-
NPN
GND
12
-
PNP
E53-Q4R4
E53-Q4Q4
E53-Q4HR4
E53-Q4HQ4H
+
11
V
L
12
-
0 to 10 V
E53-V44R4
+
11
mA
L
12
-
4 to 20mA
E53-C4R4
E53-C4DR4
A--188 Ramp/Soak Process Controller E5CK--T