E5CK-AA1-500 Datasheet, PDF (3/14 Pages) Omron Electronics LLC – Advanced, 1/16-DIN Ramp/Soak Process Controllers Ideal for Worldwide Use
J Characteristics
Indication accuracy
(See Note 1)
Thermocouple
Platinum
resistance
thermometer
Analog input
Hysteresis
Proportional band (P)
Integral (reset) time (I)
Derivative (rate) time (D)
Control period
Manual reset value
Alarm setting range
Set time
Program capacity
Programming method
Time accuracy
Sampling period
(See Note 2)
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Temperature input
Analog input
Malfunction
Destruction
Malfunction
Ambient temperature
Ambient humidity
Enclosure ratings
Memory protection
Weight
Destruction
Operating
Storage
Operating
Front panel
Rear case
Terminals
EMC
Approved standards
±0.3% of indication value or ±1°C, whichever greater, ±1 digit max.
±0.2% of indication value or ±0.8°C, whichever greater, ±1 digit max.
±0.2% of indication value, ±1 digit max.
0.01% to 99.99% FS (in units of 0.01% FS)
0.1% to 999.9% FS (in units of 0.1% FS)
0 to 3,999 s (in units of 1 s)
0 to 3,999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
--1,999 to 9,999 or --199.9 or 999.9 (decimal point position dependent on input type)
0 to 99 hrs 59 min or 0 to 99 min 59 s
1 pattern, 16 steps (possible to use up to 4 patterns with the communications func-
tion.)
Time or ramp setting method
±0.2% (±500 ms) of the set value
250 ms
100 ms
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
10 to 55 Hz, 10 m/s2 (approx. 1G) for 10 min each in X, Y, and Z directions
10 to 55 Hz, 20 m/s2 (approx. 2G) for 2 hrs each in X, Y, and Z directions
200 m/s2 min. (approx. 20G), 3 times each in 6 directions (100 m/s2 (approx. 10G)
applied to the relay)
300 m/s2 min. (30G), 3 times each in 6 directions
--10°C to 55°C (with no icing)/3-year warranty period: --10°C to 50°C
--25°C to 65°C (with no icing)
35% to 85%
NEMA 4 for indoor use (equivalent to IP66)
IEC standard IP20
IEC standard IP00
Non-volatile memory (number of writings: 100,000 operations)
Approx. 170 g;
Adapter: approx. 10 g
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
Immunity ESD:
EN61000-4-2: 4kV contact discharge (level 2)
8kV air discharge (level 3)
Immunity RF-interference:
ENV50140: 10V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900
MHz)
Immunity Conducted Disturbance: ENV50141: 10V (0.15 to 80 MHz ) (level 3)
Immunity Burst:
EN61000-4-4: 2kV power-line (level 3)
2kV I/O signal-line (level 4)
UL1092, CSA22.2 No. 14, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered
terminal cover is mounted.
Note: 1. The indication accuracy of the K1, T, and N thermocouples at a temperature of -100°C max. is ±2°C ±1 digit maximum. The
indication accuracy of the U and L thermocouples at any temperature is ±2°C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C max. is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is great-
er) ±1 digit maximum. The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or ±2°C, whichever is
greater) ±1 digit maximum.
2. The sampling period of the standard model with CT and remote SP inputs is 250 ms.
A--182 Ramp/Soak Process Controller E5CK--T