Precautions
Refer to the Technical Information for SSRs (Cat. No. J137) for gen-
eral precautions.
I Correct Use
Before Actual Operation
1. In actual operation, the G3PC may cause accidents that were
unforeseeable at the theoretical stage. Therefore it is necessary
to test the G3PC under a variety of conditions that are possible.
As for the characteristics of the G3PC, it is necessary to consider
the differences between G3PC Units.
2. The ratings in this datasheet are for testing in a temperature
range of 15 to 30°C, a relative humidity range of 25% to 85%, and
an atmospheric pressure range of 88 to 106 kPa. When testing
operation, it is necessary to confirm correct operation not only
with the actual load that will be used, but also at the same ambi-
ent conditions as for actual operation.
Mounting Method
DIN Track Mounting
When mounting to a DIN track, mount the G3PC until it clicks into
place, otherwise it become loose during use and fall. Fix both ends
with end plates.
Panel Mounting
When mounting directly to a panel, observe the following conditions:
Screw diameter: M4
Tightening torque: 0.98 to 1.47 N·m
Vertical Mounting
Horizontal Mounting
Wiring
• When using crimp terminals, observe the terminal clearances
shown below.
Main Circuit Power Supply Operating Input/Alarm Output
(Terminals 1 to 3)
(Terminals A1, A2, X1, and X2)
10
7.0
12.4
10
M3.5
• Be sure that all lead wires are of a thickness appropriate for the
current.
• The output terminals are charged, and touching them may result in
electric shock, even when the G3PC is OFF. Separate the outputs
from the power supply by installing a circuit-breaker at a higher
level in the circuit.
Tightening Torque
Be sure to tighten the screws to the specified torques given below.
Not doing so may result in malfunction.
Terminal number
A1, A2, X1, X2
1/L1, 2/T1, 3
Screw terminal
diameter
M3.5
M4
Tightening torque
0.59 to 1.18 N·m
0.98 to 1.47 N·m
Panel
Panel
Note: Use the G3PC at a load current of 50% of the rated load current
when it is mounted horizontally.
Side-by-side Mounting
Wiring duct
80 mm min.
5 mm
80 mm min.
Wiring duct
Note: Use the G3PC at a load current of 80% of the rated load current
when it is mounted side-by-side.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. J127-E1-02
In the interest of product improvement, specifications are subject to change without notice.
J-76
SSR with Failure Detection Function G3PC