G3PC_07 Datasheet, PDF (5/6 Pages) Omron Electronics LLC – SSR with Failure Detection Function
Installation
I External Specifications
Terminal Arrangement
Terminal name
Terminal number
Main circuit terminals 1/L1, 2/T1
(output)
Detection power sup- 3
ply terminal (input)
Operating circuit ter- A1, A2
minals (input)
Alarm output termi- X1, X2
nals (output)
Screw size
M4
M3.5
Indicators
Name
Status indicators
Symbol
RDY
ALM
Color
Green
Red
Input indicator INPUT
Yellow
Meaning
SSR normal
SSR failure detection
and circuit discon-
nection detection
Operating
Note: The same indicator is used as both the power supply indicator
and the alarm indicator.
Appearance
1/L1
3
A1(IN+)
A2(IN−)
X1(ALM+)
X2(ALM−)
2/T1
RDY/ALM
INPUT
I Connection Example
(See note 1.)
Display Labels
Voltage output for Temperature
Controller, sequencer
12 to 24
VDC
Input for Temperature
Controller, sequencer
30 VDC
min.
L1
1
AC
3
A1
IN
A2
X1
ALM
X2
2
T1
(See note 2.)
Heater
Note: 1. If the detection power supply terminal (terminal 3) is not connected, failure detection is not performed and so be sure to connect this
terminal.
2. If the load is connected to terminal 1/L1, failure detection may not operate correctly and so connect the load to terminal 2/T1.
3. With inductive loads (relay coil, etc.), connect back-current prevention diodes to both sides of the load.
SSR with Failure Detection Function G3PC
J-75