English
Language : 

S82J Datasheet, PDF (5/20 Pages) Omron Electronics LLC – Compact and Economical Switch mode Power Supplies with Capacities Up to 600W
Specifications
I Ratings/Characteristics
Item
100 to 240 VAC input
100 or 200 VAC
(selected automatically)
100 or 200 VAC
(selectable)
10 W
25 W
50 W 100 W (24 V) 100 W
150 W
(5, 12, 15 V)
300 W
600 W
Efficiency (typical)
67% min. (77% min. for 50-W, 24- 83% min.
V models)
75% min. 82% min.
Input
Voltage
100 to 240 VAC (85 to 264 VAC)
110 to 170 VDC (set the terminal (L) to + side)
(10 and 25 W only) (See note 1.)
100 (85 to 132) or 200 100 (85 to 132) or 200
(170 to 264) VAC
(170 to 253) VAC
(selected automatically) (selectable)
Frequency
50/60 Hz (47 to 450 Hz)
Current
(See note
2.)
100 VAC
input
200 VAC
input
0.35 A
max.
0.8 A max. 1.4 A max. 2.5 A max.
0.3 A max. 0.6 A max. 0.8 A max. 1.5 A max.
2.5 A max. 3.5 A max. 8 A max. 14 A max.
1.4 A max. 2.1 A max. 4 A max. 7 A max.
Leakage
current
(See note
2.)
100 VAC
input
200 VAC
input
0.5 mA max.
1 mA max.
Inrush cur-
rent (25°C,
cold start)
(See note
2.)
100 VAC
input
200 VAC
input
25 A max.
50 A max.
30 A max.
60 A max.
Noise filter
Yes
Output
(See note
3.)
Voltage adjustment
range
Ripple (See note 2.)
±10% (adjustable with variable resistor (V. ADJ))
2% (p-p) max.
Input variation
influence
0.4% max.
Load variation
influence
0.8% max. (with rated input, 10% to 100% load)
Temperature variation 0.05%/°C max. (with rated input and output)
influence
Startup time
500 ms max. (up to 90% of output voltage at rated input and output)
300 ms max. (up to 90%
of output voltage at rated
input and output)
Hold time (See note 2.) 20 ms min.
Additional Overload protection
function
105% to 160% of rated load current, inverted L
drop/intermittent operation type, automatic reset
105% min. of rated load current, inverted L drop
type, automatic reset (For the 600-W model, the cir-
cuit will be shut OFF when the overload exceeds 5
±3 s. Protection-ON alarm indicator lit (See note 4.))
Overvoltage
No
protection (See note 5.)
Yes
(See note 5.)
Yes (5-V out- No
put models
only) (See
note 5.)
Yes, protection-ON alarm
indicator lit (See note 4.)
Overheat protection No
Yes,
protection-
ON alarm
indicator lit
(See note 4.)
Protection-ON alarm No
indicator
Yes (color, red)
Parallel operation
No
Yes, 5 units max.
Series operation
No
Yes
Switching Power Supply S82J