CS1W-SPU01-V2 Datasheet, PDF (5/14 Pages) Omron Electronics LLC – High-speed Collection of System Data
Detailed Specifications
CS1W-SPU01-V2/02-V2
Item
Specifications
Sampling patterns
Realtime sampling: 1 pattern
Normal sampling : Up to 3 patterns
Sampling Mode
Starting methods
Any one of the following methods can be used:
• Start automatically when SYSMAC SPU Unit is started.
• Start with an SPU-Console operation.
• Start with the SYSMAC SPU Unit’s front-panel command buttons.
(Specify the command number.)
• Start from the CPU Unit’s ladder program.
Interval
User-specified intervals: ∗1
Realtime sampling: 5 ms min.
Normal sampling : 100 ms min.
Data Collection
Patterns
Basic Collection Pattern : 1 pattern (required)
Data Collection Patterns : Up to 64 patterns
Sampling
Data Storage Mode
(Unit Ver. 1.2 or later)
Starting methods
Basic Collection
Pattern (required)
Data Collection
Patterns 1 to 64
Any one of the following methods can be used:
• Start when a specified event occurs. (Use a memory event
or scheduled event. For details, see the description of
Data Collection Patterns 1 to 64 below.)
• Start automatically when SYSMAC SPU Unit is started.
• Start with an SPU-Console operation.
• Start with the SYSMAC SPU Unit’s front-panel command
buttons. (Specify the command number.)
• Start from the CPU Unit’s ladder program.
Either of the following methods can be used to start when
an event occurs:
• Memory events:
Start when a CPU Unit bit or word value matches a spec-
ified condition. Up to 500 memory events can be specified.
• Scheduled events:
Start at a specified time or time interval. Up to 16 sched-
uled events can be specified.
Interval
User-specified intervals: ∗2 ∗3
Basic Collection Pattern: 5 ms min.
Data Collection Patterns: 100 ms min.
Data Storage Mode
(Unit Ver. 2.0 or later)
Copy option
Basic Collection Pattern: Cannot be set.
Data Collection Patterns: Up to 10 patterns.
Applicable CPU
Unit I/O memory
areas
CIO Area, WR Area, HR Area, AR Area, DM Area, and EM Area banks 0 to C
Specifying I/O
memory areas
Shared Sampling Mode and
Data Storage Mode settings
Record Condition
setting
Specify the desired CPU Unit I/O memory area (data area) with a variable.
The data type can be specified with the variable.
The variables can be managed in groups.
Variable data
types
BOOL, INT, UINT, DINT, UDINT, REAL, LREAL, STRING,
CHANNEL, UINT BCD, UDINT BCD, WORD, DWORD,
CHANNEL BLOCK
Set whether or not to use a record condition.
If a record condition is used, sampling data is stored within the SYSMAC SPU
Unit only when the record condition is met. For example, sampling data can be
recorded only while a specified bit is ON or a specified word contains a particular
value (comparison).
Data exchange
with the CPU Unit
CPU Bus Unit Area
• CPU Unit to SYSMAC SPU Unit: Command execution (such as starting/stop-
ping sampling, clearing a sampling file, or saving a sampling file).
• SYSMAC SPU Unit to CPU Unit: SYSMAC SPU Unit status information
CSV files
Collected data file
format
Record contents
Indices (record number), time stamps (hh:mm:ss:ms), ns,
sampling indices (serial numbers starting at 0 when sam-
pling is started), data for each symbol delimited with com-
ma, records delimited with carriage returns
Saving files
Number of
sampling result
records stored in
one file
Any one of the following methods can be used.
• The number of records can be specified.
• A time period can be specified. (The number of records is calculated automat-
ically from the time period and interval between samples.)
• With a version 1.2 or later SYSMAC SPU Unit, the number of records can be
left unspecified. (In this case, data is added to the file until data collection is
stopped. Records are added to one file from the start of data collection until the
end.)
Scaling
Instead of directly storing the values collected from the CPU Unit’s I/O memory,
the collected values can be scaled with a linear equation or upper/lower limit
range before storage (unit version 1.2 or later).
File size
2 GB per file
Record size
Specified by user.
Number of
records
Specified by user or calculated automatically.
Saving method Data can be saved to a single file or multiple files (up to 1,200 files).
Network communications
Windows network Files in the Memory Card inserted in the PC card slot in the SYSMAC SPU Unit
shared folders
can be shared with a Windows 2000/XP/Vista personal computer.
FTP
FTP server/client provided.