CS1W-SPU01-V2/02-V2
Connecting the Power Failure Signal
CS1W-SPU01/SPU02-V2
Connect the power failure signal output line from a UPS or other device to the power failure input terminals on the SYSMAC SPU Unit.
Signals
IN
COM
IN
2 KΩ
Input indicator
MC1.5/2-STF-3.81
(Phoenix Contact)
24 VDC
COM
510 Ω
Note:Tighten the cable screws to a torque of 0.3 N·m.
Signal Input Specifications
Item
Rated input voltage
Input impedance
Input current
ON voltage
OFF voltage
Specification
24 VDC (+10% / -15%)
2 kΩ
10 mA (typical)
17.4 V min.
5 V max.
Uninterruptive Power Supply for Checking Operation
• BU70XS (OMRON) operating temperature range: 0 to 40°C
• BU606F (OMRON) operating temperature range: 0 to 55°C