E2EX5ME1 Datasheet, PDF (47/48 Pages) Omron Electronics LLC – Cylindrical Proximity Sensor
E2E/E2E2
E2E/E2E2
Example
In this example, the above conditions are checked for when the PLC
model is the C00H-ID212, the Proximity Sensor model is the
E2E-X7D1-N, and the power supply voltage is 24 V.
1. VON (14.4) x VCC (20.4 V) – VR (3 V) = 17.4 V : OK
2. IOFF (1.3 mA) y Ileak (0.8 mA)
: OK
3. ION = [VCC (20.4 V) – VR (3 V) – VPC (4 V)]/RIN (3 kΩ)
[ 4.5 mA
Therefore,
IOUT(min) (3 mA) x ION (4.5 mA)
: OK
VON: ON voltage of PLC (14.4 V)
ION: ON current of PLC (typ. 7 mA)
IOFF: OFF current of PLC (1.3 mA)
RIN: Input impedance of PLC (3 kΩ)
VPC: Internal residual voltage of PLC (4 V)
VR: Output residual voltage of Proximity Sensor (3 V)
Ileak: Leakage current of Proximity Sensor (0.8 mA)
IOUT: Control output of Proximity Sensor (3 to 100 mA)
VCC: Power supply voltage (PLC: 20.4 to 26.4 V)
The values in parentheses are for the following PLC model and
Proximity Sensor model.
PLC: C200H-ID212
Proximity Sensor: E2E-X7D1-N
Precautions for AC/DC 2-wire Proximity Sensors in Operation
Connection
Model
DC
2-wire
Connection type
AND
(serial connection)
OR
(parallel connection)
Method
Correct
Load
Correct
Load
Description
The Sensors connected together must satisfy the
following conditions.
VS – N x VR y Load operating voltage
N: No. of Sensors
VR: Residual voltage of each Sensor
VS: Supply voltage
If each Proximity Sensor is not supplied with the
rated voltage and current, the indicator will not
be lit properly or unnecessary pulses may be
output for approximately 1 ms.
The Sensors connected together must satisfy the
following conditions.
N x i x Load operating voltage
N: No. of Sensors
i: Leakage current of each Sensor
If the MY Relay, which operates at 24 VDC, is
used as a load for example, a maximum of four
Proximity Sensors can be connected to the load.
AC
AND
2-wire (serial connection)
Incorrect
Load
Correct
Load
If 100 or 200 VAC is imposed on the Proximity
Sensors, VL (i.e., the voltage imposed on the
load) will be obtained from the following.
VL = VS – (residual voltage x no. of Proximity
Sensors) (V)
Therefore, if VL is lower than the load operating
voltage, the load will not operate.
A maximum of three Proximity Sensors can be
connected in series provided that the supply
voltage is 100 V minimum.
Load
Vs y 100 V
47