General Specifications
NS Series
NS5/NS8/NS10/NS12/NS15
Series
NS5-V2
NS8-V2
NS10-V2
NS12-V2
Rated power supply
voltage
24 VDC
Allowable voltage range 20.4 to 27.6 VDC (24 VDC ±15%)
Power consumption
15 W max.
25 W max.
Ambient operating
temperature
0 to 50 °C (See note on the next page.)
90°
Note: The ambient operating temperature is subject to the following restrictions according to
the mounting angle.
Mounting angle of 0 to 30° to the horizontal:
• When no Expansion Units are mounted, the operating temperature range is 0 to 45°C.
• When a Video Input Unit or a Controller Link Interface Unit is mounted, the ambient
operating temperature is 0 to 35°C.
Mounting angle of 30 to 90° to the horizontal: Operating temperature range of 0 to 50°C
Storage temperature −20 to 60 °C *1
Ambient operating
humidity
35 to 85% (0 to 40 °C), 35 to 60% (40 to 50 °C) (with no condensation)
Operating environment No corrosive gases.
Noise immunity
Conforms to IEC61000-4-4, 2 kV (power lines).
Vibration resistance
(during operation)
10 to 57 Hz, 0.075 mm amplitude, 57 to 150 Hz, 9.8 m/s2 30 min each in X, Y, and Z directions
Shock resistance
(during operation)
Weight
Degree of protection
Ground
Battery life
Applicable standards
147 m/s2 3 times each in direction of X, Y, and Z
1.0 kg max.
2.0 kg max.
2.3 kg max.
2.5 kg max.
Front operating panel: IP65 oil-proof type and NEMA4 UL type 4. *2
Note: May not be applicable in locations with long-term exposure to oil.
Ground to 100 Ω or less.
5 years (at 25 °C): Replace battery within 5 days after the battery runs low (indicator lights orange).
Certified for conformance to UL 508, UL 1604, EMC Directive, NK, and LR Standards.
NS15-V2
45 W max.
Display surface
30°
Horizontal 0°
5 to 8.4 Hz, 3.5 mm single
amplitude, 8.4 to 150 Hz,
9.8 m/s2 10 min times
each in X, Y, and Z
directions
4.2 kg max.
*1. Operate the PT within the temperature and humidity ranges shown in the right diagram.
*2. Support for NS5, NS10, NS12 and NS15.
Operation
Storage
Humidity (%RH)
95% 80%
60
60%
NSH5 Hand-held PT
50
Temperature (°C) 40
30
20
0 10
40%
35%
20%
10%
−20 0 10 20 30 40 50 60 70 80
Temperature (°C)
Series
NSH5-V2
Type
5.7-inch Color TFT (Hand-held Version)
Case color
Black
Built-in Ethernet port No
Model
NSH5-SQR10B-V2 (Emergency stop button: Red)
NSH5-SQG10B-V2 (Stop button: Gray)
Rated power supply
voltage
24 VDC
Allowable voltage range 20.4 to 27.6 VDC (24 VDC ±15%)
Power consumption
10 W max.
Ambient operating
temperature
0 to 40°C
Storage temperature −20 to 60°C
Ambient operating
humidity
35% to 85% (0 to 40°C) with no condensation
Operating environment No corrosive gases.
Noise immunity
Common mode: 1,000 Vp-p (between power supply terminals and panel)
Normal mode: 300 Vp-p
Pulse width: 100 ns to 1 μs, Rise time: 1-ns pulse
Vibration resistance
(during operation)
10 to 57 Hz, 0.075 mm amplitude, 57 to 150 Hz, 9.8 m/s2 30 min each in X, Y, and Z directions
Shock resistance
(during operation)
147 m/s2 3 times each in direction of X, Y, and Z
Weight
1 kg max.
Degree of protection Equivalent to IP65.
Ground
Ground to 100 Ω or less.
Battery life
5 years (at 25°C): Replace battery within 5 days after the battery runs low (indicator lights orange).
Applicable standards Certified for conformance to UL 508, EMC Directive, and EN 60204-1.