English
Language : 

G3J-T-C Datasheet, PDF (4/8 Pages) Omron Electronics LLC – Solid State Contactor for 3-phase Motors with Built-in Soft Start/Stop and Monitor Output
Example of Forward/Reverse Rotation
Using Monitor Output
G3J-T-C
Three-phase, 200 to 220 V
Fuse or non-fuse breaker
Forward
rotation
Reverse
rotation
Reversible
contactor
PLC/relay-
sequential
timer circuit
A1
1 3 5 21 A1
1 3 5 21
A2 2 4 6 22
A2 2 4 6 22
L1/R L2/S
G3J-T-C
T1/U T2/V
L3/T
1
2
3
4
5
6
7
8
T3/W
Output from
PLC/relay
sequence
Output to
PLC/relay
sequence
Thermal Relay
M Motor
Note: Be sure to use a fuse or non-fuse breaker to protect the G3J.
Time Chart Example
Reversible contactor
Forward rotation signal input
(output form PLC)
Reversible contactor
Reverse rotation signal input
(output from PLC)
G3J-T-C
Input signal
(output from PLC)
G3J-T-C
Monitor output signal
(input to PLC)
Ramp-down
time
(See note.)
Ramp-down
time
Note: Switch between forward and reverse rotation only after the
motor rotation has come to a complete stop.
G3J-T-C
Monitor Output Usage Example (Motor
Stop Hold)
DC Model G3J-T@BL-C
Three-phase, 200 to 220 V
L1/R L2/S
G3J
T1/U T2/V
L3/T
1
2
3
4
5
6
7
8
T3/W
NPN Tr
Ry
12 to
24 VDC
Thermal Relay
M Motor
Brake
(non-energized)
Monitor Output Applications
• The monitor output will be ON while current is flowing to the main
circuit. Use the monitor output, e.g., to switch the operation
indicator, or to switch control signals during forward/reverse rotation
or when a mechanical brake is used.
• Be sure to use a surge absorber when connecting an inductive load
to the monitor output.
Do not use two G3J-T or G3J-C Contactors together
for reversible operation.
4