G3J-T-C Datasheet, PDF (2/8 Pages) Omron Electronics LLC – Solid State Contactor for 3-phase Motors with Built-in Soft Start/Stop and Monitor Output
Specifications
G3J-T-C
■ Certified Standards
UL 508, CSA 22.2 No. 14
■ Ratings (at an Ambient Temperature of 25°C)
Power Supply
Item
Operating input power
supply specifications
AC Model
DC Model
Rated power supply voltage
100 to 240 VAC
12 to 24 VDC
Operating voltage range
85 to 264 VAC
10.2 to 26.4 VDC
Current consumption
40 mA max. (at 100 to 240 VAC) 70 mA max. (at 12 to 24 VDC)
Operating (Input) Circuit
AC Model
Input
method
No-
voltage
input
Short-circuiting/opening terminals 3 and 1 or
terminals 3 and 2
SSR input short-circuited: Maximum
impedance of 1 kΩ,
Maximum residual
voltage of 1 V
SSR input open:
Minimum
impedance of
100 kΩ
Relay input:
For minute signals
DC Model
Input current
Input No-
method voltage
input
10 mA max. (at 12 to 24 VDC)
Short-circuiting/opening terminals 3 and 1 or
terminals 3 and 2
SSR input turned ON: Maximum residual
voltage of 2 V between
short-circuited
terminals
SSR input turned OFF:Maximum leakage
current of 0.15 mA
Relay input:
For minute signals
Main Circuit (for Both AC and DC Models)
Item
Model
G3J-T217BL-C
G3J-T211BL-C
Rated load voltage
200 to 240 VAC
Rated voltage range
180 to 264 VAC
Rated carry current (See note 1.)
17.4 A (at 40°C)
11.1 A (at 40°C)
Minimum load current
0.5 A
Inrush current resistance (peak value)
500 A (60 Hz, 1 cycle)
350 A (60 Hz, 1 cycle)
Overload resistance
Refer to Engineering Data on page 5
Closed current (effective value) AC3
174 A
111 A
AC4
208.8 A
133.2 A
Breaking current (effective value) AC3
139.2 A
88.8 A
AC4
174 A
111 A
Applicable 3-phase inductive motor (See note 2.) 200 to 220 VAC
load
(AC3, AC4, AC53-a)
3.7 kW (17.4 A)
200 to 220 VAC
2.2 kW (11.1 A)
Resistive load (AC1) (See note 3.)
200 to 240 VAC
17.4 A
200 to 240 VAC
11.1 A
G3J-T205BL-C
4.8 A (at 40°C)
150 A (60 Hz, 1 cycle)
48 A
57.6 A
38.4 A
48 A
200 to 220 VAC
0.75 kW (4.8 A)
200 to 240 VAC
4.8 A
Note: 1. The rated carry load depends on the ambient temperature. For details, refer to the Load Current vs. Ambient Temperature graph in
Engineering Data.
2. Satisfies switching test conditions of AC3, AC4, and AC53-a. (Refer to Engineering Data on page 5 for the test conditions.)
3. Single-phase loads cannot be used.
Monitor Output
Item
Operating input power AC model (See note.)
supply specifications
Rated power supply voltage 100 to 240 VAC
Operating voltage range
85 to 264 VAC
Rated carry current
50 mA
Minimum load current
3 mA
DC model (See note.)
12 to 24 VDC
10.2 to 26.4 VDC
0.2 A
3 mA
Note: Internal wiring
5
5 (+)
6
AC model
6 (−)
DC model
2