K2CM-Q2MA Datasheet, PDF (3/16 Pages) Omron Electronics LLC – Solid-state Relay Enables Choice of Three Operating Functions (Overcurrent, Openphase, and Reverse-phase)
K2CM
■ Characteristics
Variation due to
temperature
fluctuation
At 20 ±20 °C
At 20 ±30 °C
Variation due to At 85% to 110% of
voltage fluctuation rated voltage
Variation due to
frequency
fluctuation
At 95% to 105% of
rated frequency
Insulation resistance
Dielectric strength
Permissible impulse voltage
Overcurrent strength of main circuit
Overvoltage strength of control power
supply circuit
Variation due to waveform distortion
Vibration
Shock
Test current
(reference only)
Operating time
Setting
characteristics of
operating time
Service life
Ambient temperature
Humidity
Altitude
Overcurrent: ±5% of operating value, ±10% of operating time
Open-phase: ±10% of operating value, ±10% of operating time
Reverse-phase: ±10% of operating value, ±10% of operating time
Overcurrent: ±10% of operating value, ±20% of operating time
Open-phase: ±20% of operating value, ±20% of operating time
Reverse-phase: ±20% of operating value, ±20% of operating time
Overcurrent: ±5% of operating value, ±10% of operating time
Open-phase: ±5% of operating value, ±10% of operating time
Reverse-phase: ±5% of operating value, ±10% of operating time
10 MΩ min. (between current-carrying terminals and mounting panel)
5 MΩ min. (between current-carrying terminals and between contact poles)
2,500 VAC (between current-carrying terminals and mounting panel and between current-carrying
terminals)
1,000 VAC (between contact poles)
Current reverse-phase detection models:
6,000 V (between current-carrying terminals and mounting panel)
4,500 V (between current-carrying terminals and between control power supply terminals)
Waveform: 1.2/50 µs
Voltage reverse-phase detection models:
4,500 V (between current-carrying terminals and mounting panel)
Waveform: 1.2/50 µs
No abnormality develops when 20 times the set current value is applied for 2 s, 2 times with a 1-
minute interval.
No abnormality develops when 1.15 times the relay’s rated voltage is applied once for 3 hours.
No malfunction occurs when pulse containing 100% of the 2nd to 9th harmonics is applied (open-
phase switch set to “Low”). (See note.)
Malfunction: 10 to 55 Hz, 0.3-mm double amplitude (in X, Y, and Z directions for 10 minutes each)
Destruction: 10 to 25 Hz, 2-mm double amplitude (in X, Y, and Z directions for 2 hours each)
Malfunction: 98 m/s2 (approx. 10 G) in X, Y, and Z directions
Destruction: 294 m/s2 (approx. 30 G) in X, Y, and Z directions
Set time value
Approx. ±30% of the maximum setting value
Electrical: 10,000 operations
Operating: −10 to 60 °C (with no icing)
Storage: −25 to 65 °C
35% to 85%
2,000 m max.
Note: This means that no malfunction occurs with the open-phase element, but the operating value of the overload element may vary.
3