English
Language : 

S8JX-G03524CD Datasheet, PDF (24/28 Pages) Omron Electronics LLC – Wide Variety of Output Voltage Variations: 48 V for 15 to 150 W, and 5 or 12 V for 150 W
S8JX
Safety Precautions
Refer to Safety Precautions for All Power Supplies.
CAUTION
Minor electric shock, fire, or Product failure may
occasionally occur. Do not disassemble, modify, or
repair the Product to touch the interior of the
Product.
Minor burns may occasionally occur. Do not touch
the Product while power is being supplied or
immediately after power is turned OFF.
15-/35-/50-/100-/150-W Models
Standard Mounting
Standard Mounting
(Front-mounting and DIN Rail-mounting) (Bottom-mounting)
*1
*1
Fire may occasionally occur. Tighten terminal screws
to the specified torque of 1.13 N·m.
For the 5-V output terminal, tighten the terminal
screw to 1.56 N·m.
Minor injury due to electric shock may occasionally
occur. Do not touch the terminals while power is
being supplied. Always close the terminal cover after
wiring.
Minor electric shock, fire, or Product failure may
occasionally occur. Do not allow any pieces of metal
or conductors or any clippings or cuttings resulting
from installation work to enter the Product.
*2
*1
Standard Mounting
(Horizontal Mounting)
*1
*3
*2
*1
*1
*3
*2
300-W Model
Standard Mounting
(Front-mounting and DIN Rail-mounting)
*1
Precautions for Safe Use
Mounting
• Take adequate measures to ensure proper heat dissipation to
increase the long-term reliability of the Product.
• Be sure to allow convection in the atmosphere around devices when
mounting. Do not use in locations where the ambient temperature
exceeds the range of the derating curve. (except 600 W)
• The S8JX-@60024@ is designed to radiate heat by means of
forced air-flow. Do not cover the air holes (provided at fan mounted
side and the opposite side) to have enough air-cooling.
• The screws must not protrude beyond the following values inside
the Power Supply when screw holes provided on the chassis are
used.
15 W, 35 W, 50 W, 100 W, or 150 W: 4 mm min.
300 W or 600 W: 8 mm min.
Mounting screw tightening torque (recommended value) : 0.54 N·m.
• Rear mounting is possible using provided mounting bracket.
• When cutting out holes for mounting, make sure that cuttings do
not enter the interior of the Products.
• Improper mounting will interfere with heat dissipation and may
occasionally result in deterioration or damage of internal parts. Use
the standard mounting method only.
• The internal parts may occasionally deteriorate and be broken due
to adverse heat radiation. Do not loosen the screw on the side face
of the main body.
• When mounting two or more Power Supplies side-by-side, allow at
least 20 mm spacing between them.
• Provide a space of at least 20 mm back and forth when mounting
300-W and 600-W models as well.
• Use the metal plate as the mounting panel.
• Minor fire may occasionally occur. Set the input voltage switch to
the input voltage that is to be used (150-W, 5-V models only).
*2
*1
Standard Mounting
(Bottom-mounting)
*1
*3
*2
600-W Model
*1
*1
*3
*1. Convection of air
*2. 20 mm max.
*3. Use a metal plate as the mounting surface.
24