Overload Protection
The Power Supply is provided with an overload protection function that protects the power supply from possible damage by overcurrent. When the
output current rises above 105% to 175% min. of the rated current, the protection function is triggered, decreasing the output voltage. When the
output current falls within the rated range, the overload protection function is automatically cleared.
(Reference value)
15-/35-/50-/100-/150-W (12-/24-/48-V) Models
600-W Model
Intermittent operation
0
50
100
Load rate (%)
150-W, 5-V Models
0
50
100
Load rate (%)
300-W Model
Output interrupted
0
50
100
Load rate (%)
If an excessive current flows for 5 s or more, the output will be turned
OFF and simultaneously the protection-ON alarm indicator will be lit.
To reset the S8JX, turn OFF the power, leave the S8JX for at least
three minutes, and then turn it ON again.
Note: 1. When a load is connected that has a built-in DC-DC
converter, the overload protection may operate at startup
and the power supply may not start.
2. Internal parts may occasionally deteriorate or be damaged
if a short-circuited or overcurrent state continues during
operation.
3. Internal parts may possibly deteriorate or be damaged if the
Power Supply is used for applications with frequent inrush
current or overloading at the load end. Do not use the Power
Supply for such applications.