E3XA51 Datasheet, PDF (15/17 Pages) Omron Electronics LLC – Fiber-Optic Photoelectric Sensor
E3X
Precautions
s FIBER UNITS
Tightening Force
The tightening force applied to the Fiber Unit should be as
follows:
Screw-mounting Model
Spring mounting clip
Toothed washers
E3X
Fiber Connection and Disconnection
The E3X amplifier has a lever lock. Connect or disconnect the
fibers to or from the E3X amplifier using the following
procedures:
1. Connection
Lever lock
Nuts
(attachment)
Column Model
Retaining screw
(M 3 max.)
Clamping torque
3 kgf • cm max.
Fiber units
M3/M4 screw
M6 screw
2-mm dia. column
3-mm dia. column
E32-D14L
E32-T12F
E32-D12F
E32-T16
E32-R21
E32-M21
E32-L25A
Clamping torque
8 kgf • cm max. (0.78 N • m)
10 kgf • cm max. (0.98 N • m)
3 kgf • cm max. (0.29 N • m)
3 kgf • cm max. (0.29 N • m)
10 kgf • cm max. (0.98 N • m)
8 kgf • cm max. (0.78 N • m)
8 kgf • cm max. (0.78 N • m)
5 kgf • cm max. (0.49 N • m)
6 kgf • cm max. (0.59 N • m)
Up to 5 mm to the tip: 5 kgf • cm
max. (0.49 N • m)
Up to 5 mm from the tip: 8 kgf • cm
max. (0.78 N • m)
8 kgf • cm max. (0.78 N • m)
Use a proper-sized spanner.
Fiber
Insertion mark
Insert the fibers into the E3X amplifier and press the lever
lock until the amplifier clicks to lock the fibers. The fibers will
have insertion marks when they are cut with the E39-F4
(Fiber Cutter). The portion from the tips to the insertion mark
should be inserted to the E3X.
2. Disconnection
Raise the lock lever to unlock the fibers before pulling
them out.
Fiber Insertion
If the portion from the tip to the insertion mark of the fibers are
not inserted into the amplifier unit, the sensing distance will be
reduced.
Locked
Unlocked
16