D4B-1111N Datasheet, PDF (14/16 Pages) Omron Electronics LLC – Snap-action contact with certified direct opening operation certification
Application Precaution
D4B-@N
Changing the Operating Direction
Switches with Roller Levers
The operating direction of the lever can be easily
changed without using any tools. It can be set to
clockwise operation (CW) or counterclockwise
(CCW) operation.
Use the procedure given at the right to change
the operating direction.
Operating section
(on back of Head)
Operating procedure
Operating
position
mark
(arrow)
1. Remove the four Head set screws and remove the Head
from the Switch Box.
Head Cover 2. Turn the bottom of the Head toward you, press in the Head
Cover shown in the diagram at the left, and turn the Cover
clockwise or counterclockwise.
Note: The factory setting is for “CW.CCW.”
3. The “CW” setting is for clockwise operation and the “CCW”
setting is for counterclockwise operation. Set the Cover to
the desired position.
Safety Precautions
Refer to the “Precautions for All Switches” and “Precautions for All Safety Limit Switches”.
Precautions for Safe Use
• Do not use the Switch submerged in oil or water, or in locations
continuously subject to splashes of oil or water. Doing so may
result in oil or water entering the Switch interior. (The IP67 degree
of protection specification for the Switch refers to water penetration
while the Switch is submersed in water for a specified period of
time.)
• Always attach the cover after completing wiring and before using
the Switch. Also, do not turn ON the Switch with the cover open.
Doing so may result in electric shock.
Mounting
Use four M5 screws with washers to mount the standard model. Be
sure to apply the proper torque to tighten each screw. The 3-conduit
models can be mounted more securely by using the four screws plus
two 5 −0.05
−0.15
mm diameter studs, each of which has a maximum height
of 4.8 mm as shown below.
Mounting Dimensions (M5)
Standard Model
3-conduit Model
Precautions for Correct Use
Appropriate Tightening Torque
(3)
(6)
Be sure to tighten each
screw of the D4B-@N
(4)
properly, otherwise the
D4B-@N may malfunction. (1)
(5)
(2)
Type
Appropriate tightening
torque
1 M3.5 terminal screw
0.59 to 0.78 N·m
2 Cover mounting screw *
3 Head mounting screw
1.18 to 1.37 N·m
0.78 to 0.88 N·m
4 M5 body mounting screw
4.90 to 5.88 N·m
5 Connector
1.77 to 2.16 N·m
6
Lever Mounting Screws (Roller
Levers)
4.90 to 5.88 N·m
---
Cap screw
(for three-conduit models)
1.27 to 1.67 N·m
* Apply a tightening torque of 0.78 to 0.88 N·m to three-conduit
models.
60
59.3±0.1
30
40
42
Studs
27±0.1
30
5−−00..0155 dia. height: 5 max.
Changes in Actuator Mounting Position
• To change the angle of the lever, loosen the Allen-head bolts on
the side of the lever.
• The operating position indicator plate * has protruding parts which
engage with the lever, thus allowing changes to the lever position
by 90°.
• The back of the operating position indicator plate * has no
protruding parts. If this plate is turned over and attached, any angle
within a 360° range can be set. Do not turn over the plate, however,
when using the D4B-@N as a switch with a certified direct opening
mechanism. For an SUVA- or BIA-certified application, make sure
that the lever engages with the operating position indicator plate
securely so that the lever will not slip.
* The operating position indicator plate: Refer to page 7.
Changes in Head Mounting Position
By removing the screws on the four corners of the head, the head can
be reset in any of four directions. Make sure that no foreign materials
will penetrate through the head.
14