English
Language : 

E2E-X5ME2-M1 Datasheet, PDF (11/48 Pages) Omron Electronics LLC – A New Series of Easy-to-use and Tough E2E/E2E2 Models Long-size E2E2 Proximity Sensor Conforms to CENELEC
E2E-X@Y@ AC 2-wire Models
Size
M8
M12
M18
M30
Type Shielded Unshielded Shielded Unshielded Shielded Unshielded Shielded Unshielded
Item
E2E-X1R5Y@ E2E-X2MY@ E2E-X2Y@ E2E-X5MY@ E2E-X5Y@ E2E-X10MY@ E2E-X10Y@ E2E-X18MY@
Sensing distance 1.5 mm ±10% 2 mm ±10% 2 mm ±10% 5 mm ±10% 5 mm ±10% 10 mm ±10% 10 mm ±10% 18 mm ±10%
Set distance
0 to 1.2 mm 0 to 1.6 mm 0 to 1.6 mm 0 to 4.0 mm 0 to 4.0 mm 0 to 8.0 mm 0 to 8.0 mm 0 to 14.0 mm
Differential travel 10% max. of sensing distance
Sensing object
Ferrous metal (The sensing distance decreases with non-ferrous metal, refer to Engineering Data.)
Standard sensing
object
Iron, 8 x 8 x Iron,12 x 12 x Iron, 12 x 12 x Iron, 15 x 15 x Iron, 18 x 18 x Iron, 30 x 30 x Iron, 30 x 30 x Iron, 54 x 54 x
1 mm
1 mm
1 mm
1 mm
1 mm
1 mm
1 mm
1 mm
Response speed
25 Hz
Power supply
voltage (operating
voltage range)
(See note 1.)
24 to 240 VAC, 50/60 Hz (20 to 264 VAC)
Leakage current
1.7 mA max.
Control Load
output current
(See note
2.)
5 to 100 mA
5 to 200 mA
5 to 300 mA
Residual Refer to Engineering Data.
voltage
Indicator
Operation indicator (red LED)
Operation mode
Y1 Models: NO
(with sensing object Y2 Models: NC
approaching)
For details, refer to Timing Charts.
Protection circuit Surge suppressor
Ambient temperature Operating/Storage: –25°C to Operating/Storage: –40°C to 85°C (with no icing or condensation)
(See notes 1 and 2.) 70°C (with no icing or
condensation)
Ambient humidity Operating/Storage: 35% to 95% (with no condensation)
Temperature
influence
±10% max. of sensing
±15% max. of sensing distance at 23°C in the temperature range of –40°C to 85°C
distance at 23°C in the
±10% max. of sensing distance at 23°C in the temperature range of –25°C to 70°C
temperature range of –25°C
to 70°C
Voltage influence ±1% max. of sensing distance in the rated voltage range ±15%
Insulation resistance 50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength 4,000 VAC at 50/60 Hz for 1 min between current-carrying parts and case (2,000 VAC for M8 Models)
Vibration resistance 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance
500 m/s2 10 times each in X, 1,000 m/s2 10 times each in X, Y, and Z directions
Y, and Z directions
Degree of protection IEC 60529 IP67 (Pre-wired models: in-house standard for oil resistance (former JEM standard equivalent to IP67g)) (See
note 3.)
Connection method Pre-wired models (standard length 2 m), connector models
Weight Pre-wired
(packed models
state) Connector
models
Approx. 60 g
Approx. 15 g
Approx. 70 g
Approx. 25 g
Approx. 130 g
Approx. 40 g
Approx. 175 g
Approx. 90 g
Material Case
Stainless steel (SUS303) Brass-nickel plated
Sensing
surface
PBT (polybutylene terephthalate)
Clamping Brass-nickel plated
nuts
Toothed
washer
Iron-zinc plated
Accessories
Instruction manual
Note 1. When supplying 24 VAC to any of the above models, make sure that the operating ambient temperature range is over –25°C.
2. When using an M18-or M30-sized E2E within an ambient temperature of 70°C to 85°C, make sure that the E2E has a control output of 5
to 200 mA max.
3. This OMRON in-house standard confirms resistance to cutting and other oils. It is equivalent to the former JEM standard.
E2E/E2E2 Cylindrical Proximity Sensor
11