English
Language : 

G3NA-6 Datasheet, PDF (10/14 Pages) Omron Electronics LLC – Solid State Relays (600 VAC Models)
High-capacity Heat Sink (Y92B-P250N)
DIN-track Mounting
• Assembled DIN Tracks are heavy. Mount the DIN Tracks securely.
Be sure that the Heat Sink is securely locked to the DIN Track.
• Attach End Plates (PFP-M, order separately) to both ends of the
Units on the DIN Track to hold them in place.
• To mount a Heat Sink to a DIN Track, press down at the point
indicated by arrow 1 in the diagram and then press in the Heat Sink
at the point indicated by arrow 2.
Vertical
Applicable DIN Track
Mounting is possible on TE35-15Fe (IEC 60715) DIN tracks. DIN
tracks from the following manufacturers can be used.
Manufacturer
Schneider
WAGO
PHOENIX
Thickness: 1.5 mm
AM1-DE2000
210-114 or 210-197
N35/15
Thickness: 2.3 mm
---
210-118
N35/15/15-2.3
Direct Mounting
• Prepare mounting holes as shown in the diagram.
Tightening torque: 0.98 to 1.47 N·m
64±0.3
130±0.3
Noise Terminal Voltage According to
EN55011
The G3NA-UTU complies with EN55011 standards when a capacitor
is connected to the load power supply as shown in the following
circuit diagram.
3 m max.
C1
Input
G3NA-UTU
type
Output
Capacitor C2
• G3NA-6@@: 0.5 µF, 500 VAC
Load
C2
Capacitor C1
0.1 µF
Varistor
• G3NA-6@@: 910 V, 0.8 W
• Connect capacitor C1 to both sides of the input terminals for a
G3NA with a DC input.
• Connect capacitor C2 to both sides of the load power supply
output.
• Connect the varistor to both sides of the G3NA output terminals.
• Do not use an input line that is longer than 3 m.
Loss Time
The loss time will increase when the G3NA is used at a low applied
voltage or current. Be sure that this does not cause any problems.
Loss time
Using DC Loads
For a DC or L load, a diode should be connected in parallel the load
to absorb the counter electromotive force of the load.
Input
SSR
Load
Load power
supply
Four, 4.5 dia. or M4 holes
Operating Conditions
• Do not apply currents exceeding the rated current otherwise, the
temperature of the G3NA may rise excessively.
• As protection against accidents due to short-circuiting, be sure to
install protective devices, such as fuses and no-fuse breakers, on
the power supply side.
• Do not apply overvoltages to the input circuit or output circuit.
Failure or burning may result.
• Do not drop the G3NA or otherwise subject it to abnormal shock.
Malfunction or failure may result.
• Keep the cooling system running continuously during the ON/OFF
operation of the SSR. This is to allow residual heat to dissipate
while the SSR is OFF.
476
Solid State Relays (600 VAC Models) G3NA-6