English
Language : 

D1U3CS-D-1600-12-HC4EC Datasheet, PDF (4/5 Pages) Murata Manufacturing Co., Ltd. – 81mm Front End DC-DC Power Converter
D1U3CS-D-1600-12-HC4EC Series
81mm Front End DC-DC Power Converter
WIRING DIAGRAM FOR OUTPUT
D1U3CS
+12VRS (Main Output Remote Sense)
Dotted lines show optional remote sense connections.
Optional remote sense lines can be attached to a load that is a distance
away from the power supply to improve regulation at the load.
+12VRS (Main Output Remote Sense)
B2
+12V OUT
PB4-6
PB1-3 +12V GND
A2 +12VRS_RETURN
B3 +12V_ISHARE
12V load
+12V OUT PB4-6 B2
+12V GND PB1-3
+12VRS_RETURN A2
+12V_ISHARE B3
D1U3CS
A5,B5,C5,D5
A1
A6,B6,C6,D6
+VSB
PS_ON_L
+VSB load
FET, BJT, wire
or switch (debounced )
+VSB GND to turn on +12V main output
+VSB A5,B5,C5,D5
PS_ON_L A1
+VSB GND A6,B6,C6,D6
B4 PS_INHIBIT/PS_KILL
PS_INHIBIT/PS_KILL B4
CURRENT SHARING NOTES
1. Main 12VDC Output: Analogue active share bus. The ISHARE bus (Pin B3) must be connected on all sharing modules.
It is not required that the SENSE signals are connected to the remote load for current share to operate correctly.
2. Up to eight (8) power modules can be connected in parallel (non-redundant) or N+1 configuration. The current share bus is analogue bi-directional (can source or sink voltage representation of the current on
the ISHARE bus.
The voltage of the bus would measure 8VDC for a single power module at 100% load; for two (2) modules sharing a common load the ISHARE bus voltage would be 4V for a perfect 50/50 current share scenario.
3. The VSTANDBY output of power modules can also be connected in parallel and have internal output isolation devices; however the combined available power is limited to that available from a single power
module (3.3V; 20W) irrespective of the number of modules connected in parallel.
www.murata-ps.com/support