English
Language : 

D1U3CS-D-1600-12-HC4EC Datasheet, PDF (2/5 Pages) Murata Manufacturing Co., Ltd. – 81mm Front End DC-DC Power Converter
D1U3CS-D-1600-12-HC4EC Series
81mm Front End DC-DC Power Converter
OUTPUT CHARACTERISTICS
Parameter
Remote Sense (Main Output)
Output Rise (Monotonic)
Startup Time
Transient Response
Current Sharing Accuracy
Hot Swap Transients
Hold Up Time2
Conditions
Overall compensation at full load; +VE & -VE connections
10% to 95% rise time
DC Ramp Up
PS_ON activation
12V, 50%-100% or 100%-50% step load; 1A/μs slew rate
3.3SB 50-100% or 100%-50% step load 1A/μs slew rate
At 100% load (between sharing modules; up to 8 in parallel)
FL (Full Load)
2 Assumes deployment on systems with dual redundant “A” and “B” DC input feeds
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Altitude (no derating at 40°C)
Altitude (no derating at 50°C)
Shock
Sinusoidal Vibration
MTBF
Conditions
Non-Condensing
1600W Output Power
Non-Condensing
Non-Operating
Operational, 0.5G; 5-500Hz
Telcordia SR-332 M1C1 @ 40°C
CSA/CSA-C22.2 No.60950-1-07 2nd Ed, Amendment 1:2011
Safety Approvals (Standards)
ANSI/UL Std. No. 60950-1-2011
IEC 60950-1:2005, (2nd Edition) + A1:2009
CE Marking per LVD DIRECTIVE 2006/95/EC
Input Fusing
Switching Frequency
Material Flammability
Weight
Internal 60A/170Vdc fast blow fuse on the DC line input
70KHz for the Boost Converter; 240KHz for the Main Output Converter
UL94-V0
Min Typ Max Units
120 mV
No positive voltage excursion
1.5 2.5
s
200
ms
±600
mV
±165
±10 %
±5
%
1
ms
Min Typ
-40
0
5
5
3000
1800
Max Units
70
°C
50
95
%
90
m
30
G
395
K Hours
2.84/1.31 lbs/kg
PROTECTION CHARACTERISTICS
Output
Parameter Conditions
N/A
Over-Temp Auto re-start
Over-Voltage Latching; toggle PS_ON or recycle DC input to reset
Min. Typ. Max. Units
57
60
63
°C
13.3
14.5
V
For slow overload events a constant current will be sustained for 1sec followed by a latch off that will auto
12V (Main)
Over-Current
reset in 5secs. For hard (short circuit) events the output will shut down within 50ms and auto restart within
200ms. This cycle will be repeated ten times at which point the output will permanently latch off. The power
140
module will require to be reset by recycling the incoming DC source or “toggling” PS_ON.
160
A
3.3VSB
Over-Voltage Latching; toggle PS_ON or recycle DC input to reset
Over-Current Shutdown followed by auto-recovery
3.9
4.3
V
6.5
9.0
A
ISOLATION CHARACTERISTICS
Parameter
Isolation
Conditions
Input to Output - Basic
Output to Chassis (Ground)
Min. Typ. Max. Units
1000
Vdc
500
Vdc
STATUS INDICATORS
Conditions
No incoming DC supply present; power module completely unpowered (off).
Standby Rail ON; Main Output OFF; DC input present & correct
Standby Rail ON; Main Output ON
Main Output overcurrent; undervoltage, overvoltage warning
FAN_FAULT; overtemperature; standby rail overcurrent, Main Output overcurrent or overvoltage
LED Status
LED not illuminated
Blinking Green
Solid Green
Blinking Amber
Solid Amber
www.murata-ps.com/support
D1U3CS-D-1600-12-HC4EC.A02 Page 2 of 5