English
Language : 

D1U54-HD-1200-12-HA4C Datasheet, PDF (5/8 Pages) Murata Power Solutions Inc. – 54mm 1U Front End HVDC Power Supply Converter
TIMING SPECIFICATIONS
Power Removal Holdup
D1U54-HD-1200-12-HA4C
54mm 1U Front End HVDC Power Supply Converter
Power Removal Timing
Vsb holdup
V1 holdup (Effective Total)
HVDC fail detect
PWOK delay off
PWOK Hold Up
Min
100ms
12ms
-
1.0ms
11.0ms
Max Notes
-
- 100% load
30ms
100% load
100% load
PW_OK
EMISSIONS AND IMMUNITY
Characteristic
Conducted Emissions
ESD Immunity
Radiated Field Immunity
Electrical Fast Transients/Burst Immunity
Surge Immunity
RF Conducted Immunity
Magnetic Field Immunity
Voltage Dips, Interruptions
Standard
FCC 47 CFR Part 15/CISPR 22/EN55022
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
TBD
DERATING CURVE
Compliance
Class A with 6dB margin
Level 4 criteria A
Level 3 criteria B
Level 3 criteria B
Level 3 criteria A
Level 3 criteria A
3 A/m criteria B
Output Current De-rating vs Ambient Temperature
(Back to Front Airflow)
D1U54-HD-1200-12-HA4C
110
100
90
80
70
60
50
40
30
20
10
0
25
30
35
40
45
50
55
60
Ambient Temperature (°C)
230VDC
www.murata-ps.com/support
d1U54-hd-1200-12-ha4c.a01 Page 5 of 8