English
Language : 

D1U54-HD-1200-12-HA4C Datasheet, PDF (2/8 Pages) Murata Power Solutions Inc. – 54mm 1U Front End HVDC Power Supply Converter
D1U54-HD-1200-12-HA4C
54mm 1U Front End HVDC Power Supply Converter
OUTPUT CHARACTERISTICS
Parameter
Remote Sense (Main Output)
Output Rise (Monotonic)
Conditions
Overall compensation at full load; +VE & -VE connections
10% to 95% rise time
DC Ramp Up
Startup Time
PS_ON activation
12V, 50-100% or 100-50% step load; 1A/μs slew rate
Transient Response
5VSB 50-100% or 100-50% step load 1A/μs slew rate
Current Sharing Accuracy (between sharing
modules; up to 8 in parallel)
30% -100% load
Hot-Swap Transients
Hold-Up Time
100% Load; 230VDC nominal input prior to hold up
Min.
Typ.
Max.
Units
120
mV
No positive voltage (overshoot) excursion
3
s
200
ms
±600
mV
±250
mV
-7
+7
%
-5
+5
%
12
ms
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Altitude (no derating at 40°C)
Shock
Sinusoidal Vibration
MTBF
Safety Approvals – Pending Submission
Input Fuse
Weight
Conditions
Min.
Typ.
Max.
Non-Condensing
-40
70
1200W Output
-5
50
Non-Condensing
5
90
5
95
3000
Non-Operating
30
Operational, 0.5G; 5-500Hz
Telcordia SR-332 M1C1 @ 40°C
529
CAN/CSA C22.2 No 60950-1-07, Am.1:2011, Am2:2014
UL 60950-1-2014, 2nd Ed.
IEC60950-1:2005 (2nd ED.)+A1:2009+A2:2013
EN60950-1:2006+A11+A1+A12+A2
Power Supply has internal dual 10A/420Vdc rated fast acting fuses on the DC (positive and negative) lines
3.15 lbs (1.43Kg)
Units
°C
%
m
G
K Hours
lbs/kg
PROTECTION CHARACTERISTICS
Output Voltage Parameter
Over-Temperature
Over-Voltage
12V (Main) Over-Current
Over-Voltage
5VSB
Over-Current
Conditions
Air inlet temperature; auto restart
Latching; toggle PS_ON or recycle DC input to reset
Shutdown followed by auto-recovery
Latching; toggle PS_ON or recycle DC input to reset
Shutdown followed by auto-recovery
Min.
Typ.
60
65
13
110
5.4
3.3
Max.
Units
70
°C
14.2
V
130
A
6.0
V
4.5
A
ISOLATION CHARACTERISTICS
Parameter
Insulation Safety Rating / Test Voltage
Isolation
Conditions
Input to Output - Reinforced
Input to Chassis - Basic
Output to Chassis
Min.
Typ.
Max.
Units
4242
Vdc
2121
Vdc
500
Vdc
STATUS INDICATORS AND CONTROL SIGNALS
Condition
Standby - ON; Main output - OFF; DC PRESENT
Standby - ON; Main output - ON
Main output overcurrent, undervoltage, overvoltage
FAN_FAULT; overtemperature; standby overcurrent, undervoltage
No HVDC Input Power
Power Supply Warning Event
GREEN
LED Status (Power)
Blinking green
Solid green
Off
Off
Off
Off
AMBER
LED Status (Fault)
Off
Off
On
On
Off
Blinking
www.murata-ps.com/support
d1U54-hd-1200-12-ha4c.a01 Page 2 of 8