English
Language : 

D1U86P Datasheet, PDF (3/6 Pages) Murata Power Solutions Inc. – 86mm 1U Front End AC-DC Power Supply
D1U86P-W-1600-12-HBxDC Series
86mm 1U Front End AC-DC Power Supply
EMISSIONS AND IMMUNITY
Characteristic
Input Current Harmonics
Voltage Fluctuation and Flicker
Conducted Emissions
ESD Immunity
Radiated Field Immunity
Electrical Fast Transient Immunity
Surge Immunity
Radiated Field Conducted Immunity
Magnetic Field Immunity
Voltage dips, interruptions
Standard
IEC/EN 61000-3-2
IEC/EN 61000-3-3
FCC 47 CFR Part 15/CISPR 22/EN55022
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-4-11
Compliance
Complies
Complies
Class A, 6dB margin
Level 3 criteria A
Level 3 criteria B
Level 3 criteria A
Level 3 criteria A
Level 3 criteria A
3 A/m criteria B
230Vin, 100% load, Phase 0°, Dip 100% Duration 10ms (A)
230Vin, 50% load, Phase 0°, Dip 100% Duration 20ms (VSB:A, V1:A)
230Vin, 100% load, Phase 0°, Dip 100% Duration > 20ms (VSB, V1:B)
STATUS INDICATORS AND CONTROL SIGNALS
Signal
Description
PSON#
Low = main output on; PSON# can be permanently tied to GND within the host system.
PRESENT#
Short pin pulled down on p/s; pulled up to either 3.3V or 12V (max) in the host system. For 3.3V use a 5.11KΩ resistor; for 12V,
use a 21KΩ resistor.
PS INTERRUPT
Open drain PMBus™ signal; can be left open if not used.
ADDR
PMBus™ Address; ADDR can be grounded or left open if not used. If grounded, the address will be 000, if it is open, the default
address will be 111.
ISHARE
Analog representation of main output current; can be left open if not used.
PSOK4
A three level signal based on AC input and DC output status; can be left open if not used.
I2C CLOCK
I2C clock
I2C DATA
I2C data
LED State
Mode
Operating Condition
1. Off
AC Turn-off
AC Input is below minimum power-supply turn-on specification
2. Green – blinking 1Hz
Standby
Power supply standby output is operating within normal parameters and main output is disabled
3. Green – solid
Power-good
Power supply standby & main outputs are operating within normal parameters and delivering power
4. Yellow – blinking 1Hz
Warning
Warning condition in power supply has been detected
5. Yellow – solid
Fault
Fault condition in power supply has been detected.
3 See truth table below for operation.
OUTPUT CONNECTOR AND SIGNAL SPECIFICATION
Pin#
14-26, 39-51
1-13, 52-64
37
38
36
35
34
33
32
31
30
29
28
27
Function
RTN
12V
12VSB
PSINTERRUPT
PRESENT#
PSOK
ISHARE
PSON#
SCL
SDA
GND
N/A
N/A
ADDR
Pin Type
Power Ground
Power
Power
Output
Input
Analog output
Analog I/O
Input
Input
I/O
Analog I/O
N/A
N/A
Analog input
Description
Power and Standby Return
12V Output
12V Standby Output
Active low; interrupt line for power supply
fault & warning detection as per PMBus spec
Power Supply Present Signal (shortest pin)
Combination of there power supply output
indicator signals:
1. AC input OK
2. Power Good
3. Power Supply Fault
Analog representation of main output current.
Typical analog voltage shall be 60.15mV/Amp
of main output current.
Power Supply on/off control signal
SMBus/PMBus Clock
SMBus/PMBus Data
Power Supply Signal Ground
Reserved; no User connection
Reserved; no User connection
PMBus Address
Power Supply Output Card Edge
64
1
33
PCB Top Side
32
PCB Bottom Side
www.murata-ps.com/support
D1U86P-W-1600-12-HBxDC.A01 Page 3 of 6