English
Language : 

D1U86P Datasheet, PDF (2/6 Pages) Murata Power Solutions Inc. – 86mm 1U Front End AC-DC Power Supply
D1U86P-W-1600-12-HBxDC Series
86mm 1U Front End AC-DC Power Supply
OUTPUT CHARACTERISTICS
Parameter
Conditions
Min.
Typ.
Max.
Units
Output Rise Monotonicity
No voltage excursion
Startup Time
AC ramp up
1.5
3
s
Transient Response
12V, 50% load step, 1.0Aμs di/dt
12VSB, 50% load step,1.0Aμs di/dt
600
mV
600
Current sharing accuracy (up to 8 in parallel)3
At 100% load
±5
%
Hot Swap Transients
All outputs remain in regulation
5
%
Holdup Time
At full load
12
ms
3 Load current of 100% applies to each power module max load connected in an N+1 configuration; therefore the total load will be “N” x 100% . The share accuracy of ±5% is a fixed percentage irrespective
of total loading and number of units connected in parallel.
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Altitude (without derating at 45°C)
Shock
Vibration
MTBF
Acoustic
Safety Approvals
Input Fuse
Weight
Conditions
Noncondensing
30G non operating
10-500Hz, 0.5G (non-operational)
Per Telcordia SR-322 M1C1@ 40°C
Min.
Typ.
-40
0
5
5
3000
559K
CSA 60950-1-07+A1:2011
ANSI/UL 60950-1-2011, Second Edition
IEC 60950-1:2005 (2nd Edition) + A1:2009
EN 60950-1:2006 +A11:2009 +A1:2010
Power Supply has internal 16A/250V fast blow fuse on the AC line input
Max.
Units
85
°C
55
90
%
95
m
hrs
65
dBA/@1m
2.33/1.06 lbs/Kg
PROTECTION CHARACTERISTICS
Output
Voltage
Parameter
Overtemperature (intake)
Overvoltage
Overcurrent at 220Vac
12V
Overcurrent at 120Vac
Overvoltage
12VSB
Overcurrent
Conditions
Min.
Typ.
Max.
Units
An OTP warning will be issued via the PMBus™
interface when the air inlet exceeds 65°C;
however the power module shall not shut down
65
°C
until critical internal hotspot temperatures are
exceeded.
Latching
13.2
Shutdown of the output followed by auto- recovery
after one second. The output shall attempt three
140
such auto-recovery attempts and then enter a per-
manent latched state. Recovery of the permanent
latched state shall require cycling of the incoming
118
AC source or toggling of the PSON# signal.
Latching
13.2
Autorecovery
2.75
14.4
V
153
A
129
14.4
V
3
A
ISOLATION CHARACTERISTICS
Parameter
Insulation Safety Rating / Test Voltage
Isolation
Leakage Current
Conditions
Input to Output - Reinforced
Input to Chassis - Basic
Output to Chassis
1.5mA at 264Vac, 50/60Hz
Min.
Typ.
Max.
Units
3000
Vrms
1500
Vrms
500
Vdc
www.murata-ps.com/support