D1U54 Datasheet, PDF (3/9 Pages) Murata Power Solutions Inc. – 54mm 1U Front End DC-DC Power Supply Converter
D1U54-D-650-12-HBxC Series
PROTECTION CHARACTERISTICS
54mm 1U Front End DC-DC Power Supply Converter
Output Parameter
Conditions
Min. Typ. Max. Units
Overtemperature
Overvoltage
12V
Overcurrent (Target)
12VSB
Overvoltage
Overcurrent
Autorestart with 4°C hysteresis for recovery (warning issued at 70°C)
Latching
13
The output shall shutdown when an overcurrent condition is detected.
It will auto restart after 1sec; however if the overcurrent condition is redetected the output will once again
shutdown.
The output will once again re-start, however if the overcurrent condition persists it will latch of after the fifth 60
unsuccessful attempt.
To reset the latch it will be necessary to toggle the PS_ON_L signal (B4) or recycle the incoming DC source.
Latching
13.0
The output shall shutdown when an overcurrent is detected.
It will auto restart after 2sec; however if the overcurrent is re-detected the output will once again shutdown. 2.2
This cycle will occur indefinitely while the overcurrent condition persists.
75
°C
14.5 °C
70 A
14.5 V
2.8 A
ISOLATION CHARACTERISTICS
Parameter
Insulation Safety Rating
Isolation
Conditions
Input to Output
Input to Chassis
Output to Chassis
Min.
Typ.
Max.
Units
1000
Vdc
1000
Vdc
500
Vdc
EMISSIONS AND IMMUNITY
Conducted Emissions
FCC 47 CFR Part 15/CISPR 22/EN55022
Class A with 6dB margin
ESD Immunity
IEC/EN 61000-4-2
Level 4 criteria A
Radiated Field Immunity
IEC/EN 61000-4-3
Level 3 criteria B
Electrical Fast Transients/Burst Immunity IEC/EN 61000-4-4
Level 3 criteria B
Surge Immunity
IEC/EN 61000-4-5
±1kV common mode and differential mode, unit passes criteria A (normal
performance)*
RF Conducted Immunity
IEC/EN 61000-4-6
Level 3 criteria A
Magnetic Field Immunity
IEC/EN 61000-4-8
3 A/m criteria B
Voltage Dips, Interruptions
----
-53Vin, 80% load, Dip 100% Duration 4ms,Criteria (A)
* Impedance is 2 ohms for differential and common mode.
STATUS INDICATORS
LED NAME
Input
Input
Input
LED MODE
OK
OV/UV WARNING
OFF OR FAULT
LED STATE/OPERATION
Solid Green
Blinking Green
Off
DESCRIPTION
Input voltage operating within normal specified range
Input voltage operating in:
1) overvoltage warning, or
2) undervoltage warning range
Input voltage operating:
1) above overvoltage range, or
2) below undervoltage range, or
3) not present
Output
POWER GOOD
Solid Green
Main output and standby output enabled with no power supply warning or fault
detected
Output
STANDBY
Blinking Green
Standby output enabled with no power supply warning or fault detected
Output
WARNING
Blinking Amber
Power supply warning detected as per PMBus STATUS_X reporting bytes
Output
FAULT
Solid Amber
Power supply fault detected as per PMBus STATUS_X reporting bytes
LED fault/warning operation follows PMBus fault/warning reporting status flags and will thus also be 'sticky' (i.e. even if actual fault/warning is cleared, LED will still be in FAULT or WARNING mode until PMBus status flags
are cleared with the CLEAR_FAULTS command
www.murata-ps.com/support
D1U54-D-650-12-HBxC.A02 Page 3 of 9