English
Language : 

D1U54 Datasheet, PDF (1/9 Pages) Murata Power Solutions Inc. – 54mm 1U Front End DC-DC Power Supply Converter
D1U54-D-650-12-HBxC Series
54mm 1U Front End DC-DC Power Supply Converter
PRODUCT OVERVIEW
The D1U54-D-650-12-HBxC products are very high efficiency DC input 650 watt front end supplies provided with a
12V main and a 12V Standby output. An active (analogue) current share characteristic is provided to allow units to be
operated in parallel. The power supply may be hot plugged; recovers from overtemperature faults, and has status
LEDs on the front panel in addition to hardware signal logic and PMBus™ status signals. The low profile 1U package
and 21.4W/cubic inch power density make them ideal for delivering reliable, efficient power to networking
equipment, workstations, storage systems and other 12V distributed power architectures.
ORDERING GUIDE
Part Number
Murata Internal Power Output
Part Number -44 to -72Vdc
D1U54-D-650-12-HB3C
D1U54-D-650-12-HB4C
M1879
M1878
650W
Main
Output
12Vdc
Standby
Output
12Vdc
Airflow
Front to Back
Back to front
FEATURES
 650W output power
 93% efficiency at 50% load
 12V main output
 12V standby output
 1U height:
 2.15" x 9.00" x 1.57"
 54.5mm x 228.6mm x 40mm
 21.4 Watts per cubic inch density
 N+1 redundancy capable, including hot plugging
 Active (analogue) current sharing on 12V main
output; ORING FET
 Overvoltage, Overcurrent, Overtemperature
protection
 Internal cooling fan (variable speed)
 PMBus™/I2C interface with status indicators
 RoHS compliant
 Two Year Warranty
www.murata-
ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at: www.murata-ps.com/en/3d/acdc.html
INPUT CHARACTERISTICS
Parameter
Conditions
Input Source Voltage Operating Range
Turn-on Input Voltage
Ramp up
Turn-off Input Voltage
Ramp down
Input current at Vin = -53Vdc
650W
Inrush Current
Cold start (25°C) between 0 to 200ms
Min.
-44
-42.5
-37.5
20% load
90
Efficiency (-53Vdc) excluding fan load 50% load
93
100% load
92
Nom. Max. Units
-53 -72 Vdc
-43 -43.5
-38 -39.5 Vdc
13.6
Adc
25
Apk
%
OUTPUT VOLTAGE CHARACTERISTICS
Nominal
Output
Voltage
Parameter
Conditions
Min.
Typ.
Max. Units
Output Set Point Accuracy 50% load; Tamb =25°C 11.96 12.00 12.04 Vdc
Line and Load Regulation
Setpoint; temperature;
line and load
-1.0%
+1.0
%
%
12V Ripple Voltage & Noise1, 2
20MHz Bandwidth
Output Current Range
0
120 mV p-p
54.2 A
Load Capacitance
500
4000 μF
Output Set Point Accuracy 50% load; Tamb = 25°C 11.96 12.00 12.04
Line and Load Regulation
Setpoint; temperature;
line and load
11.7
12VSB Ripple Voltage & Noise1
20MHz Bandwidth
12.3 Vdc
120 mV p-p
Output Current
0
2
A
1 Ripple and noise is measured with a parallel combination 0.1μF of ceramic and 10μF of tantalum capacitance on each
measurement node.
2 Measurements assume the use of the minimum load capacitance as specified for the main 12V output and a minimum load of 5%.
Below 5% loading the overall voltage deviation shall be within ±2.5%.
For full details go to
www.murata-ps.com/rohs
CB
Test Certificate
and Test Report
www.murata-ps.com/support
D1U54-D-650-12-HBxC.A02 Page 1 of 9