D1U4-W-1600-54-HBXC Datasheet, PDF (3/6 Pages) Murata Power Solutions Inc. – AC-DC Power Supply
PROTECTION CHARACTERISTICS
Output
Voltage
Parameter
Over-Temperature
54V
Over-Voltage
Over-Current
Over-Voltage
12VSB
Over-Current
ISOLATION CHARACTERISTICS
Parameter
Insulation Safety Rating / Test Voltage
Isolation
Grounding
STATUS INDICATORS AND CONTROL SIGNALS
Status
LED Indicators
I2C and PMBus
SYS_CONTR
EMISSIONS AND IMMUNITY
Characteristic
Input Current Harmonics
Voltage Fluctuation & Flicker
Conducted Emissions
Radiated Emissions
ESD Immunity
Radiated Field Immunity
Electrical Fast Transients/Burst Immunity
Surge Immunity
RF Conducted Immunity
Magnetic Field Immunity
Voltage Dips & Interruptions
D1U4-W-1600-54-HBxC
AC-DC Power Supply
Conditions
Auto re-start
Latching
Constant Current for 200ms
followed by latch
Latching
Latching
Min.
Typ.
Max.
Units
55
65
°C
57
60
V
33
39
A
13.5
14.4
V
2.2
2.6
A
Conditions
Min.
Typ.
Max.
Units
Input to Output - Reinforced
3000
Vrms
Input to Chassis - Basic
1500
Vrms
Output to Chassis (Ground)
2250
Vdc
The Main 54VDC output shall be provided with isolation between the output and chassis ground. It shall be able
to withstand the following tests:
a) 1500VRMS at 50Hz to 60Hz for 60s.
b) 2250 VDC for 60s.
There shall be no insulation breakdown during the test as defined in sub clause 5.2.2 of IEC 60950-1:2001. The
resistance after the test should be at least 2M ohms when measured at 500VDC.
The VRTN should be isolated from the 12VSB Return and the power module shall support PoE Electrical Isolation
Requirements.
Conditions
Description
Off
No AC applied to any power module in host system
Off
Blinking Green
No AC applied to this power module only
AC Present & VSTANDBY “on”
Green
54VDC and VSTANDBY “on” and “OK”
Blinking Amber
Amber
Power Module Warning
Power Module Failure
There is provision for the connection of dual I2C buses for redundancy.
This enables two master devices to connect to single slave device(s) within the power module.
The power module is provided with a PMBus Management Interface that provides status, measurement and
control data.
Host system control input that can be used to turn on/off the Main 54VDC Output.
Standard
IEC/EN 61000-3-2
IEC/EN 61000-3-3
FCC 47 CFR Part 15; CISPR 22; EN55022
IEC/EN 61000-4-2;
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-4-11
Compliance
Complies with Class A Limits
Complies
Complies to Class A with 6dB margin
Complies to Class A with 6dB margin
4KV Contact discharge; Criteria A
8KV Operational air discharge; Criteria A
15KV non-operational air discharge, Criteria A
Complies
Complies
1KV/2KV; Criteria A performance
3VAC, 80% AM, 1KHz; Criteria A performance
3A/m
Complies
www.murata-ps.com/support
CPS_D1U4-W-1600-54-HBxC.A01 Page 3 of 6