English
Language : 

D1U4-W-1600-54-HBXC Datasheet, PDF (1/6 Pages) Murata Power Solutions Inc. – AC-DC Power Supply
www.murata-ps.com
D1U4-W-1600-54-HBxC
AC-DC Power Supply
FEATURES
1600W Output Power
1.6"(1U) x 14.0" x 4.0"
(41.0mm x 355.6mm x 101.6mm)
54VDC Main; PoE compatible
12V SB Output
PMBus™ Power Management Bus supported by
dual redundant I2C interfaces.
N+1 Redundancy Capable; hot swap (up to 8
modules in parallel)
Active current sharing on 54VDC Main output;
integral bidirectional MOSFET output isolation
device
Over-Voltage, Over-Current; Over-Temperature
Protection
Internal variable speed cooling fans
20ms full cycle hold up
RoHS Compliant
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at
www.murata-ps.com/en/3d/acdc.html
PRODUCT OVERVIEW
The D1U4-W-1600-54-HBxC is a 1600W power factor corrected (PFC) front end power module intended for hot swap
redundant systems. There is a main output of 54VDC (floating with respect to chassis ground) and a 12VDC Standby/
bias output (that is present whenever the incoming AC source is applied.
The form factor is suitable for 1RU chassis enclosures and is designed to deliver reliable bulk DC power to servers,
workstations, storage systems, PoE switches or any 54VDC distributed power architecture requiring high power
density.
The high efficiency design supports speed controlled dual DC fans in a thermally optimized package that is self-pro-
tecting and able to auto recover from over-current and over-temperature events. Visual status information is provided
via front panel mounted LED indicators in addition to hardware logic signals and a PMBus™ management interface.
ORDERING GUIDE
Model Number
Power Output High
Line AC
Power Output Low
Line AC
Main Output
Standby
Output
Airflow
D1U4-W-1600-54-HB4C
D1U4-W-1600-54-HB3C
1600W
1200W
Back to front
54V
12V
Front to back
INPUT CHARACTERISTICS
Parameter
Input Voltage Operating Range
Input Frequency
Turn-on Input Voltage
Turn-off Input Voltage
Maximum Current @ VIN = 200Vac
Maximum Current @ VIN = 90Vac
Inrush Current
Power Factor
Conditions
Ramp Up
Ramp Down
1600W
1200W
Cold start between 0 to 1ms
At 230Vac; FL
Min. Typ. Max. Units
90 115/230 264 Vac
47 50/60 63
Hz
81
89
Vac
70.5
78.0
10
Arms
15
100 Apk
0.95
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage
Parameter
Conditions
Min. Typ. Max. Units
Voltage Set Point
Line & Load Regulation
54V
Vdc
52.38
55.62
54V Output Current
0
30
A
Ripple Voltage & Noise1
20MHz Bandwidth
540 mVp-p
Load Capacitance
3800
24,000 μF
Voltage Set Point
Line & Load Regulation
12
Vdc
11.64
12.36
12V Output Current
0
2
A
Ripple Voltage & Noise1
20MHz Bandwidth
33 mVp-p
Load Capacitance
1530
μF
1 Ripple and noise are measured with a parallel combination of a 0.1μF ceramic capacitor and 2 x 270μF OSCON
capacitors on each of the power module outputs measurement nodes. See test set up diagram below.
Ḥ
For full details go to
www.murata-ps.com/rohs
www.murata-ps.com/support
CB
Test Certificate
and Test Report