English
Language : 

D1U4-W-1600-54-HBXC Datasheet, PDF (2/6 Pages) Murata Power Solutions Inc. – AC-DC Power Supply
RIPPLE MEASUREMENT
D1U4-W-1600-54-HBxC
AC-DC Power Supply
Power Supply
AC Phase
2x270uF OSCON
AC Ground
0.1uF Ceramic
Load Box
BNC to BNC Shielded Cable
General Notes:
1. Load the outputs at specified minimum
output current.
2. Connect the probe as shown with the
input tip and ground as short as possible.
3. Take all measurements
4. Repeat the measurements with the
outputs at specified maximum output
current.
Oscilloscope
20MHz BW
OUTPUT CHARACTERISTICS
Parameter
Remote Sense
Efficiency
Output Rise (Monotonic)
Startup Time
Transient Response
Current Sharing Accuracy (up to 8 in parallel)
Hot Swap Transients
Hold Up Time
Conditions
Min.
Typ.
Max.
Units
Remote sense is not enabled on these variants due to the System Control feature and the relatively wide line &
load regulation window.
230Vac (excluding fan)
90
%
10% to 95% rise time
Overshoot less than 10% for all outputs; no negative transition at
turn off.
AC Ramp Up
3
s
PS_ON activation
250
ms
54VDC 50% step (50-100%; 100%-50%)
load; 1A/μs
±2700
mV
12VSB 1A/μs
±250
At 100% load
±10
%
5
%
100% load 230Vac nominal
20
ms
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Altitude
Shock
Operational Vibration
MTBF
Safety Approvals
Input Fusing
Weight
Conditions
Min.
Typ.
Max.
Non-Condensing
-40
70
0
50
Non-Condensing
10
90
5
90
3000
Non-Operating
30
Operational, 0.5G; 5-500Hz
Telcordia SR-332 40°C
630
CAN/CSA-C22.2 No.60950-1-07 Am 1:2011
ANSI/UL 60950-1-2011
IEC60950-1:2005 (2nd Ed)+A1:2009 and EN60950-1:2006/A11:2009/A1:2010/A12:2011
CQC GB4943,1-2011
Internal 20A/250V rated fast blow in AC line
4.63/2.1
Units
°C
%
M
G
K Hours
lbs/kg
www.murata-ps.com/support