English
Language : 

D1U3CS-W-1300F-12-HX4EC Datasheet, PDF (2/5 Pages) Murata Power Solutions Inc. – 81mm Front End AC-DC Power Converter
D1U3CS-W-1300F-12-Hx4EC Series
81mm Front End AC-DC Power Converter
OUTPUT CHARACTERISTICS
Parameter
Remote Sense
Output Rise (Monotonic)
Startup Time
Transient Response
Current Sharing Accuracy (up to 8 in parallel)
Hot Swap Transients
Hold Up Time
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Altitude (no derating at 40°C)
Shock
Sinusoidal Vibration
MTBF
Safety Approvals (Standards)
Input Fusing
Switching Frequency
Material Flammability
Weight
PROTECTION CHARACTERISTICS
Output Voltage
N/A
12V (Main)
3.3VSB
5VSB
Parameter
Over-Temperature
Over-Voltage
Over-Current (1300W)
Over-Current (1200W)
Over-Voltage
Over-Current
Over-Voltage
Over-Current
ISOLATION CHARACTERISTICS
Parameter
Insulation Safety Rating/Test Voltage
Isolation
Conditions
Min Typ Max Units
Compensation at full load (total loop for positive & negative connections)
120 mV
10% to 95% rise time
No voltage excursion
AC Ramp Up
1.5 2.5
s
PS_ON activation
150
ms
12V, 50-100% step load 1A/μs
3.3/5VSB 50-100% step load 1A/μs
600
mV
165/250
At 100% load
±7
%
5
%
FL (Full Load)
12
ms
Conditions
Non-Condensing
1200W
1300W
Non-Condensing
Operating
Operational, 2.0G; 5-500Hz
Telcordia SR-332 M1C1 @ 40°C
CSA/UL C22.2 No.60950-1-07, Amendment 1_2011
ANSI/UL 60950-1-2011
IEC 60950-1:2005, (2nd Edition) + A1:2009
EN 60950-1:2006 + A11:2009 +A1 :2010 +A12:2011
CE Marking per LVD DIRECTIVE 2006/95/ECS
Internal 16A/250V rated fast blow in AC line
90KHz for the PFC Boost Converter
130KHZ for the Main Output Converter
UL94-V0
Min Typ
-40
0
0
5
5
3000
500
Max Units
70
50
°C
40
90
%
95
m
30
G
K Hours
3.15/1.43 Lbs/kg
Conditions
Auto re-start
Latching
Latching
Latching
Latching
Auto-recovery
Latching
Auto-recovery
Min. Typ. Max. Units
57
60
63
°C
13.3
14.5
V
115
125
A
108
118
3.9
4.3
V
6.5
9.0
A
5.6
6.0
V
5.0
6.5
A
Conditions
Input to Output – Re-enforced
Input to Chassis - Basic
Output to Chassis (Ground)
Min. Typ. Max. Units
3000
Vrms
1500
Vrms
500
Vdc
www.murata-ps.com/support