English
Language : 

TA100PW Datasheet, PDF (3/5 Pages) MORNSUN Science& Technology Ltd. – Isolated Transmitter
Isolated Transmitter
TAxxxPW series
Application Precautions
1. Please read the instructions carefully before use; contact our technical support if you have any problem;
2. Do not use the product in hazardous areas;
3. Use DC power supply for the product. and 220V AC power supply is prohibited;
4. Do not disassemble or assemble the product without permission to avoid explosion protection failure or malfunction of product.
Design Reference
1. Wiring diagram for product application
8 Ins id e
7 O uts id e
10 Ins id e
O uts id e
9
12 Ins id e
11 O uts id e
6 I ns id e
5 O uts id e
4 I ns id e
O uts id e
3
2 I ns id e
O uts id e
1
Bott om power supply port
Note: When us e bottom power supply, anyone group or both is OK.
Programmable analog signal isolator
PIN
Description (2 input 2 output)
1
Signal 2 input-
2
Signal 2 input+
5
Signal 1 input-
6
Signal 1 input+
7
Signal 1 output-
8
Signal 1 output+
9
Signal 2 output-
10
Signal 2 output+
11
power input-
12
power input+
Programmable analog signal isolator with isolation power output
Distributor wiring method
PIN Description
(2 input 2 output)
1 Signal 2 isolated input-
2 Signal 2 isolated input+
3/
4/
5 Signal 1 isolated input-
6 Signal 1 isolated input+
7 Signal 1 output-
8 Signal 1 output+
9 Signal 2 output-
10 Signal 2 output+
11 power input-
12 power input+
Isolator
wiring
method
Description
(2 input 2 output)
Signal 2 input+
/
Signal 2 input -
Signal 1 input -
Signal 1 input +
/
Signal 1 output-
Signal 1 output+
Signal 2 output-
Signal 2 output+
power input-
power input+
Fie ld
Ar ea
2- Wire
Ci rcui t
Tr ansd ucer
TA1x0PW
6
Cha nnel 1
5
4 GND
11 12
Powe r
C on t r ol
Ar ea
8
Cha nnel 1
7
DCS
PLC
Fie ld
A r ea
2- Wire
Ci rcui t
Tr ansd ucer
TA1x5PW
6
Cha nnel 1
5
4 GND
11 12
Powe r
Contr ol
A r ea
8
Cha nnel 1
7
DC S
PLC
2014.02.18-A/2
Page 3 of 5
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation