English
Language : 

DS75LV Datasheet, PDF (6/13 Pages) Maxim Integrated Products – Digital Thermometer and Thermostat
DS75LV: Digital Thermometer and Thermostat
OPERATION¾THERMOSTAT
The DS75LV thermostat has two operating modes, comparator mode and interrupt mode, which activate and
deactivate the open-drain thermostat output (O.S.) based on user-programmable trip-points (TOS and THYST). The
DS75LV powers up with the thermostat in comparator mode, active-low O.S. polarity, over-temperature trip-point
(TOS) register set to 80 C, and the hystoresis trip-point (THYST) register set to 75 C. If these power-up settings are
compatible with the application, the DS75LV can be used as a standalone thermostat (i.e., no 2–wire
communication required). If interrupt mode operation, active-high O.S. polarity or different TOS and THYST values are
desired, they must be programmed after power-up, so standalone operation is not possible.
In both operating modes, the user can program the thermostat fault tolerance, which sets how many consecutive
temperature readings (1, 2, 4, or 6) must fall outside of the thermostat limits before the thermostat output is
triggered. The fault tolerance is set by the F1 and F0 bits in the configuration register. At power-up the fault
tolerance is set to 1.
The data format of the TOS and THYST registers is identical to that of the temperature register (see Figure 3), i.e., a
two-byte two’s complement representation of the trip-point temperature in degrees centigrade with bits 3 through 0
hardwired to 0. After every temperature conversion, the measurement is compared to the values stored in the TOS
and THYST registers. The O.S. output is updated based on the result of the comparison and the operating mode of
the IC. The number of TOS and THYST bits used during the thermostat comparison is equal to the conversion
resolution set by the R1 and R0 bits in the configuration register. For example, if the resolution is 9 bits, only the 9
MSbs of TOS and THYST will be used by the thermostat comparator.
The active state of the O.S. output can be changed via the POL bit in the configuration register. The power-up
default is active low.
If the user does not wish to use the thermostat capabilities of the DS75LV, the O.S. output should be left floating.
Note that if the thermostat is not used, the TOS and THYST registers can be used for general storage of system data.
Comparator Mode: When the thermostat is in comparator mode, O.S. can be programmed to operate with any
amount of hystoresis. The O.S. output becomes active when the measured temperature exceeds the TOS value a
consecutive number of times as defined by the F1 and F0 fault tolerance (FT) bits in the configuration register. O.S.
then stays active until the first time the temperature falls below the value stored in THYST. Putting the device into
shutdown mode does not clear O.S. in comparator mode. Thermostat comparator mode operation with FT = 2 is
illustrated in Figure 4.
Interrupt Mode: In interrupt mode, the O.S. output first becomes active when the measured temperature exceeds
the TOS value a consecutive number of times equal to the FT value in the configuration register. Once activated,
O.S. can only be cleared by either putting the DS75LV into shutdown mode or by reading from any register
(temperature, configuration, TOS, or THYST ) on the device. Once O.S. has been deactivated, it will only be
reactivated when the measured temperature falls below the THYST value a consecutive number of times equal to the
FT value. Again, O.S can only be cleared by putting the device into shutdown mode or reading any register. Thus,
this interrupt/clear process is cyclical between TOS and THYST events (i.e, TOS, clear, THYST, clear, TOS, clear, THYST,
clear, etc.). Thermostat interrupt mode operation with FT = 2 is illustrated in Figure 4.
6 of 13